Manifold Pressure Adjustment; Main Valve Solenoid Connections - A.O. Smith SERIES 120 Service Handbook

Commercial gas water heaters
Hide thumbs Also See for SERIES 120:
Table of Contents

Advertisement

Manifold Pressure Adjustment

The main gas regulators are found beneath the silver or black cap screws. (Natural Gas
valves have silver caps; Propane valves have a black caps). Remove the caps to access
the outlet (manifold) pressure adjustment screw. IMPORTANT: Ensure that the outlet
pressure matches the manifold pressure that is listed on the water heater rating plate.
Natural Gas valves are factory preset to 3.5 inches W.C. The full rate outlet pressure
range is between 3 and 5 inches W.C.
Propane (LP) valves are factory preset to
range is between 8 and 12 inches W.C.
Caution: Always test the manifold pressure at the outlet when the gas is flowing.
Wiring Harness
Lead Wires
(24-Volt Main Valve
Solenoid Connections)

Main Valve Solenoid Connections

The figure above shows the two 24-volt main valve (MV) solenoid connections. The two
yellow wires from the 12-pin ignition board plug connect to these leads.
Servicing should only be performed by a Qualifi ed Service Agent
OPERATION AND SERVICE
10.0 inches W.C. The full rate outlet pressure
TOP VIEW OF GAS VALVE
Figure 13
17
Main Gas
Regulators
(Outlet Pressure
Adjustment)