8-3. ELECTRIC CHARACTERISTICS

Indoor unit
Model Name
Outdoor unit
Voltage
Power Supply
Frequency
Mode
Rated Value
Current
Input
Max Operating Current
Starting Current
Main Fuse (Circuit breaker)
Current
*1) Wiring Spec
Power Cable
*2)Limited wiring length
Input
Indoor Fan Motor
Full Load Amp.
Input
Outdoor Fan Motor
Full Load Amp.
Indoor unit
Model Name
Outdoor unit
Voltage
Power Supply
Frequency
Mode
Rated Value
Current
Input
Max Operating Current
Starting Current
Main Fuse (Circuit breaker)
Current
*1) Wiring Spec
Power Cable
*2)Limited wiring length
Input
Indoor Fan Motor
Full Load Amp.
Input
Outdoor Fan Motor
Full Load Amp.
*1) Wiring Spec :
Selected Sample
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
When the wiring length becomes long, please select the wiring of a more larger
diameter.
AU*24LUAR
AO*24LMAKL
V
Hz
Cooling
A
11.1
kW
2.53
A
12.5
10
A
A
2
m
m
m
kW
0.153
0.64
A
0.15
kW
0.73
A
AU*36LUAS
AO*36LMAWL
V
Hz
Cooling
17.6
A
4.01
kW
17.9
A
15
A
A
2
m
m
m
0.19
kW
1.00
A
0.13
kW
A
08-07
AU*30LUAS
AO*30LMAWL
230
50
Heating
Cooling
12.5
10.5
2.86
2.40
15.2
12.5
10
15
25
4.0
33
0.19
1.00
0.13
0.42
AU*45LUAS
AO*45LJBYL
230
50
Heating
Cooling
15.2
19.5
3.49
4.45
18.2
22.6
15
15
30
4.0
21
0.23
1.35
0.067 x 2
0.42
0.34 x 2
Heating
12.4
2.84
14.8
15
30
4.0
27
Heating
17.3
3.95
20.0
15
30
6.0
27