4 Planning

4.1 FC721 system limits and options

FC721
Detector line
Max. C-NET addresses
Number of loops or stubs
Number of devices per loop
Number of devices per stub line
Supply
Power supply
Batteries (with 70 W power unit)
Battery extension (optional)
External DC 24 V supply
Operating unit
Inputs and outputs
RT alarm, relay
RT fault, relay
RT alarm monitored
RT fault monitored
Outputs for monitored, acoustic signal transmitter
Freely configurable inputs/outputs
Options
RS232/RS485 module
Ext. Printer DL3750+
LED module; 24 red/green and yellow LEDs each
EVAC-NL operating unit [NL]
License key S1
Kaba or Nordic key switch
Building Technologies
Fire Safety
* Note system limits!
The description of system components and options does not form part of this
technical manual.
FC721 system limits and options
System limits
126 *(1 loop or 2 stubs)
1 loop or 2 stubs
Max. 126
Max. 32
70 W
Max. 2x 7 Ah
Max. 2x 26 Ah
with optional power supply (150 W) and additional
empty housing (standard)
Integrated
Max. 1
Max. 1
Max. 1
Max. 1
Max. 1
Max. 1
Planning
1
1
1
1
1
4
19 | 118
A6V10211100_f_en_--
2015-12-15
4