11.4 Replacing non-stationary C-NET devices of the
11.4.1 Replacing the C-NET device
Building Technologies
Fire Safety
Replacing non-stationary C-NET devices of the same type
same type
Procedure
●
Switching on test mode
●
Replace C-NET device
●
Switch on normal operation
●
Connect PC to the 'Station'
●
Load configuration from the 'Station' to the PC
●
Disconnect PC from the 'Station'
You will find information about the individual steps in the following chapters and the
chapters to which reference is made below.
1. Remove the C-NET device you want to replace from the base.
2. Wait approx. 20 seconds.
3. Insert the new C-NET device of the same type.
The internal alarm indicator flashes for 10 seconds following successful
replacement.
Proceed as follows if the alarm indicator does not flash:
1. Ensure that you wait long enough before inserting.
2. Check whether other C-NET devices are missing on the detector line.
3. Check whether a device that is not of the same type has been inserted. If this is
the case, insert a device of the same type.
4. Restart the C-NET line.