Excel 50
CONTROLLER
INSTALLATION INSTRUCTIONS
EN1B-0101GE51 R1000

Advertisement

Table of Contents
loading

Summary of Contents for Echelon Excel 50

  • Page 1 Excel 50 CONTROLLER INSTALLATION INSTRUCTIONS EN1B-0101GE51 R1000...
  • Page 2 ORKS LonTalk, LonUsers, LonPoint, Neuron, 3120, 3150, the Echelon logo, the L logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, and LonMaker are trademarks of Echelon Corporation.
  • Page 3: Table Of Contents

    EXCEL 50 INSTALLATION INSTRUCTIONS CONTENTS Revision overview ..................................5 General ......................................5 Safety Instructions ....................5 Hardware Overview....................6 Version Overview...................... 6 Dimensions ....................... 7 Mounting......................................8 Housing........................8 Front Door ......................8 Inside Cabinet without MMI .................. 9 Inside Cabinet with MMI ..................10 Application Module....................
  • Page 4 EXCEL 50 INSTALLATION INSTRUCTIONS Cable Specifications................... 27 Modem or ISDN Terminal Adapter Connections ..........27 Changing Between MMI and Modem Connection ..........27 Remote Communications ................................28 Modem Requirements .................... 28 No Set-up for Standard Modem Behavior............... 28 Automatic Baudrate Synchronization..............28 Auto / Manual Answer Detection ................
  • Page 5: Revision Overview

    Instructions are to be observed. Disconnect the power supply before you start to in- • The Excel 50 Controller may be installed and mounted stall the Excel 50 Controller. Do not reconnect the only by authorized and trained personnel.
  • Page 6: Hardware Overview

    Slave Power RS232C RX TX Fig. 5. Application module. Fig. 6. Meter-Bus adapter. Fig. 1. Excel 50 Controller housing. Fig. 7. Mounting accessories. Fig. 2. Screw terminal blocks. Version Overview *Version can be upgraded by firmware. Firmware with Housing: integrated modem communication is available for down- loading to the controller.
  • Page 7: Dimensions

    EXCEL 50 INSTALLATION INSTRUCTIONS Dimensions 7.79 in. (198 mm) LCD DISPLAY FAST ACCESS APPLICATION KEYS MODULE BASIC FUNCTION KEYS 2.76 in. (70 mm) C-BUS PORT 2.83 in. (72 mm) 3.19 in. (81 mm) STANDARD DIN-CUTOUT CUTOUT 7.32 in. (186 mm) 4.17 in.
  • Page 8: Mounting

    EXCEL 50 INSTALLATION INSTRUCTIONS MOUNTING If the Excel 50 Controller has an MMI, the housing is Insert the rubber sealing ring into the gap around the mounted either in the front door of a cabinet or on a DIN-rail front plate of the Excel 50 Controller.
  • Page 9: Inside Cabinet Without Mmi

    EXCEL 50 INSTALLATION INSTRUCTIONS Inside Cabinet without MMI Attach Front Door Mounting clamps on both sides of the controller and tighten the screws with a screwdriver Break plastic tabs covering the slots on the controller as is shown in Fig. 12.
  • Page 10: Inside Cabinet With Mmi

    EXCEL 50 INSTALLATION INSTRUCTIONS Inside Cabinet with MMI The screw terminal blocks and the switch for the bus ter- mination cannot be accessed after the controller with MMI is mounted on the DIN-rail. Although the Flat Strip cables and the Bus Terminal socket...
  • Page 11: Installation

    EXCEL 50 INSTALLATION INSTRUCTIONS INSTALLATION With the Excel 50, two different types of input/output ter- Table 3. Flat Strip Cables. minals can be used: Screw terminal blocks for direct wiring and Phoenix terminal blocks for remote wiring within the Length For Phoenix same cabinet.
  • Page 12: Block B

    EXCEL 50 INSTALLATION INSTRUCTIONS Table 4. Translation table for screw to Phoenix Block B terminal numbering. Block A Block B Screw Phoenix Screw Phoenix +10V/5mA REF. +10V/5mA REF. DI-POWER DI-POWER AGND AGND Fig. 20. Phoenix Terminal Fig. 19. Screw Terminal Block B.
  • Page 13: Cabling

    EXCEL 50 INSTALLATION INSTRUCTIONS Cabling Cable Routing Cable Lengths and Cross Sectional Areas All signal (input/output, low voltage) cables are communi- Table 6. Signal types and cross-sectional areas. cation circuits in accordance with VDE 0100, VDE 0800 and local regulations and should therefore be routed separately...
  • Page 14: Analog Inputs

    Wind sensor WS21 Further connections: Temperature sensor terminal TF26 Solar Sensor SAF 25 VMP Feedback Potentiometer The characteristic curves for other types of sensors can be entered manually in the data point description (see Excel 50 User Guide, EN2B-137). EN1B-0101...
  • Page 15 EXCEL 50 INSTALLATION INSTRUCTIONS Table 7. Accuracy of analog inputs with NTC sensors Firmware Release 2.03.xx and older Range Deviation / ± Kelvin (without sensor tolerance) 10 Vdc max. 10 mA NTC (20k ohms) -58 to <-40°F (-50 to <-40°C) 5.5 K...
  • Page 16: Digital Inputs

    EXCEL 50 INSTALLATION INSTRUCTIONS Digital Inputs Technical Description Parameter requirements: If the digital inputs are used for normal digital or analog signals, the signals have to meet the static and dynamic requirements stated in Table 8 and Table 9. If three out of four digital inputs are used as totalizers, the...
  • Page 17: Analog Inputs

    Analog outputs can be used, for example, to operate valve or damper actuators. The characteristic curves for these actuators can be defined via MMI (see Excel 50 User Guide). Each analog output can also be used as a digital output.
  • Page 18: Digital Outputs

    EXCEL 50 INSTALLATION INSTRUCTIONS Digital Outputs Technical Description Connection Examples The digital outputs are switched by a triac that can be connected directly to an external relay. Technical Specification Number: Six digital outputs Output stages: Low signal High signal 24 Vac Fig.
  • Page 19: Power Supply

    EXCEL 50 INSTALLATION INSTRUCTIONS Power Supply The Excel 50 Controller is powered by an external trans- 1450 Series former. All transformers of the 1450 series are designed for 50/60 Hz Transformer requirements for one Excel 50 Controller: AC and have insulated accessory outputs. The transformers include built-in fuses, line transient/surge protection and AC 24 Vac ±20%...
  • Page 20: Screw Terminal Block Installation

    — Do not connect line power supply directly to the cables to and from sensors, actuators, valves, relays, terminals. etc. you want to connect to the Excel 50 Controller from — Insulate devices with 120 Vac / 230 Vac by a Table 6.
  • Page 21: Phoenix Terminal Block Installation

    Choose the minimum cross sectional areas for all terminals. cables to and from sensors, actuators, valves, relays, etc. you want to connect to the Excel 50 Controller from — Insulate devices with 120 Vac / 230 Vac by a Table 6.
  • Page 22: Adjusting The Mmi Display Contrast

    EXCEL 50 INSTALLATION INSTRUCTIONS Fig. 40. Connecting the power supply. IMPORTANT If there already are additional transformers, for example supplying actuators or active sensors: — Connect the 24 Vac (-) (secondary side) of the transformers together. Plug the flat strip cables into the sockets of the terminal blocks and the housing as is shown in Fig.
  • Page 23: Communication

    Excel Building Supervisor (XBS) and other compatible components can also be connected (Excel IRC EXCEL 5000 devices via the C-Bus. The Excel 50 Controller Multicontroller; Excel EMC; Modem Device XM 100A). also has the capability to communicate with devices on a network.
  • Page 24: C-Bus Extension By Using Repeaters

    EXCEL 50 INSTALLATION INSTRUCTIONS Table 18 summarizes cable types and gives selection Choose a suitable C-Bus cable from Table 18. guidance. Note that baud rate and maximum bus length are IMPORTANT related to each other. Make sure that all bus devices connected to the same C-Bus are set to the same baud rate otherwise Table 18.
  • Page 25: Lon Works Network Interface

    EXCEL 50 INSTALLATION INSTRUCTIONS Network Interface ORKS Excel 50 Controllers may be equipped with an application module (see Table 15) containing an FTT-10A Free Topology Table 21. Free topology (singly-terminated) Twisted Pair Transceiver which allows communication with specifications. other device on a L network.
  • Page 26: Lon Works Service Led Diagnostics

    Pushing the L service button will force a new ORKS commissioning of the Excel 50. While commissioning, LED L2 continuously illuminates red for less than 1 minute and afterwards return to the normal state (L2 = OFF). A more detailed diagnosis can be carried out by observing the duration of the ON and OFF states of the service LED in connection with power ON / OFF.
  • Page 27: Controller Serial Port

    MMI activates again. Fig. 51. Modem connection. Cable Specifications The serial port of the Excel 50 controller accepts a standard modem cable with a female 9-pin connector. Use the cable Ready-made cables with the shield already connected to the that is supplied with the modem/ISDN terminal adapter.
  • Page 28: Remote Communications

    The Excel 50 Controller will automatically detect the device device connected to the computer serial port or using the (MMI or modem) attached to the serial port and set the Windows™...
  • Page 29: Set-Up For Limited Communication Speed

    CAUTION engine) is required and must be connected directly to the serial port of the Excel 50 controller. The M20T translates the Users are advised to NOT use the M20T in auto- Excel CPU data received in transparent mode into the GSM motive service stations.
  • Page 30: Serial Cable

    EXCEL 50 INSTALLATION INSTRUCTIONS Serial Cable HANDSET INTERFACE For connecting the M20T to the Excel controller, a standard RS232 cable (9-pin V24 sub-D sockets) is required. GSM Antenna Requirements All major suppliers of GSM antennas can supply GSM900 Antennas with FME plugs to connect with the M20 Terminal MOUNTING HOLES for a variety of applications.
  • Page 31: Gsm Antenna Installation

    EXCEL 50 INSTALLATION INSTRUCTIONS check the reception with the SIEMENS AT com- mands – see the M20T handbook. — An alternative way to verify the signal quality is to use the terminal program on the CD supplied with the M20T. You will find a special button on it that allows checking on the signal quality.
  • Page 32 EXCEL 50 INSTALLATION INSTRUCTIONS 12. You may now enter the PIN number or let the Excel CPU do this. If you want to enter the PIN number now, enter the PIN with the command AT+CPIN=”xxxx”, where xxxx represents the PIN number.
  • Page 33: Meter-Bus Connection

    CAUTION Fig. 57. Mounting of PW3. Never connect V- of the PW3 to pin 2 of the Excel 50 Connect Meter-Bus devices to PW3 Meter-Bus Controller and V+ to pin 1. This could cause damage Adapter. See Table 26 for a list of supported devices.
  • Page 34 EXCEL 50 INSTALLATION INSTRUCTIONS LEDs POWER, GRN METER BUS TxD, YEL C-BUS TxD, YEL C-BUS RxD, YEL METER BUS RxD, YEL C-BUS TERMINATION SWITCH 4 5 6 METER BUS (RJ45 JACK) Fig. 60. PW3 Meter Adapter power connections. C-BUS Meter-Bus activity can by monitored using the LEDs on the HE01 application module (see Fig.
  • Page 35: Start-Up Sequence

    CARE applications is similar but does not include the C-Bus after start-up. entry of configuration codes. See the Excel 50 User Move the cursor to the 'NEXT' field with the ARROW keys. Guide, EN2B-137, for more details.
  • Page 36: B-Port

    EXCEL 50 INSTALLATION INSTRUCTIONS The contents of this listbox will depend upon the exact hard- Move the cursor to the 'BACK' field with the arrow keys. ware configuration of the controller. The listed interfaces to Confirm with ENTER. be configured will be from among the following: LON-Bus (i.e.
  • Page 37: Select Application

    Confirm with ENTER. The number of entries (trend samples) that can be stored in If the Excel 50 controller is connected to a C-Bus, unless the buffer for Remote Building Central A is determined by a using the HE01 application module (bus number appended...
  • Page 38: Request Download

    An alarm “Invalid User ID” will be issued. C7>-1 C8>-1 Datapoint Wiring Check NOTE If the 'LIZARD-Excel 50 Application Selector' is not >Contr. Setup available, please contact your local Honeywell >Select Applic. branch for support.
  • Page 39 EXCEL 50 INSTALLATION INSTRUCTIONS user addr. < > >Default Points STATE/VALUE: >Alarm History >0 Select Press ENTER to select the value. Change the value/state using the '+' or '–' keys. Confirm with ENTER. — 'Default Points' to display I/O points for checking values and manually setting outputs for testing.
  • Page 40 EXCEL 50 INSTALLATION INSTRUCTIONS Home and Building Control Home and Building Control Home and Building Control Products Honeywell Inc. Honeywell Limited-Honeywell Limitee Honeywell AG Honeywell Plaza 155 Gordon Baker Road Böblinger Straβe 17 Manufacturing P.O. Box 524 North York, Ontario D-71101 Schönaich...