6.5.17 Optimum start/stop control

Optimum start/stop control puts forward in time the change of operating level against
the scheduled point in time, thereby giving consideration to the building dynamics
(heating-up time and cooling down time). This ensures that the required temperature
level is reached at the scheduled point in time. If this is not the case (too early or too
late), a new changeover point is calculated, which is used the next time.
Line no.
HC1
HC2
HC3
790
1090
1390
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint is reached at the respective switching time.
Line no.
HC1
HC2
HC3
791
1091
1391
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint minus ¼ °C is reached at the respective switching time.
TRx
Figure 25: Optimum start/stop control
Line no.
Meaning
TRw
Room temperature setpoint
TRx
Actual value of room temperature
Xoff
Forward shift of switch-off time
Xon
Forward shift of switch-on time
ZSP
Time program
Note!
The time of optimization (forward shift) can be limited to a maximum, separately for
optimum start and optimum stop control. When setting the time of optimization to 0,
the function is deactivated. Optimum start/stop control is possible with or without
room sensor.
User Manual LMS14...
6 The settings in detail
Operating line
Optimum start control max
Operating line
Optimum stop control max
Xoff
1/4 °C
CC1U7471en