Siemens 7KG6106 Operating Instructions Manual page 22

Simeas-t series with auxiliary power for alternating voltage or alternating current rms with expanded start/end range and non-linear characteristic curve
Table of Contents

Advertisement

SIMEAS-T - Transducer with auxiliary power
Transducer with expanded start range and suppressed end range
Example: Transducer with range:
0 to 0.05 to U
0 to 0.8 to A
EN ≙
Basic settings
R32: Stop left
R33: Stop right
Break point
Feed U
= 0.05 U
E
EN
Set A = 0.8 A
± 0.05% A
N
Then turn trim potentiometer R32 to the right until the output value A increases.
Full-scale value
Feed U
= U
± 0.05% U
E
EN
output value A = A
N
Transducer with suppressed start range and expanded end range
Example: Transducer with range:
0 to 0.8 to 1.2 U
EN ≙
Basic settings
R32: Stop left
R33: Stop right
Break point
Feed U
= 0.8 U
± 0.05% U
E
EN
the output value A = 0.2 A
Then turn trim potentiometer R32 to the right until the output value A increases.
Full-scale value
Feed U
= 1.2 U
± 0.05% U
E
EN
the output value A = A
22
N
± 0.05% U
, set the output value with trim potentiometer R51
EN
.
N
, set the
EN
± 0.05% A
with trim potentiometer R33.
N
0 to 0.2 to A
N
, set
EN
± 0.05% A
N
N
, set
EN
± 0.05% A
with trim potentiometer R33.
N
N
with trim potentiometer R51.