Problem
Motor Stalls
Motor runs and
then dies down
Motor does not
come up to speed
Motor takes too
long to accelerate
Wrong Rotation (3
Phase)
Motor Overheats
Motor Vibrates
MUA-SVX005B-EN
Probable
Solution
Cause
Motor overloaded
Reduce load or replace motor.
With a 3 phase
Check line for open phase.
power source, one
phase may be
open
Defective capacitor
Replace capacitor.
Wrong application
Consult manufacturer.
Overloaded motor
Reduce load or replace motor.
Low line voltage.
Check across AC line and correct if possible.
Partial loss of line
Check for loose connections. Determine
voltage
adequacy of main power supply.
Motor undersized
Replace with larger motor.
for application
Voltage too low at
Check across AC line and correct if possible.
motor terminals
Line wiring to
Install larger line wiring.
motor is too small
Excessive load
Replace with larger motor.
Loose connection
Check connections and tighten where
necessary.
Improperly wired
Check unit wiring diagram. Reverse any two
to AC line (wrong
line voltage connections.
sequence of
phases)
Motor overloaded
Replace with larger motor.
Motor ventilation
Clean motor.
clogged
Motor (3 phase)
Check to insure that all connections are tight.
may have open
phase
Line voltage too
Check across AC line and correct if possible.
high or too low
Worn blower
Replace blower bearings.
bearings.
Motor mounting
Tighten mounting bolts.
bolts loose
Driven equipment
Balance driven equipment.
unbalanced
Worn motor
Replace motor.
bearings.
3 phase Motor
Check for open circuit and correct.
running on single
phase