CHAPTER 4: SETPOINTS

Initiate

FASTPATH:
FASTPATH:
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DROPOUT DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.100 s
The setting is used to set the period of time for which the Breaker Fail output is sealed-in.
This timer must be coordinated with the automatic reclosing scheme of the failed
breaker, to which the Breaker Failure element sends a cancel reclosure signal. Reclosure
of a remote breaker can also be prevented by holding a transfer Trip signal on for longer
than the reclaim time.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
For details see
Common
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
Path:
Setpoints > Control > Breaker Failure 1 > BF1 Initiate
EXTERNAL INITIATE
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand that initiates the Breaker Failure scheme;
typically the trip signals from external devices.
The trip signals from internal protection functions may be used with the help of FlexLogic,
but for easier setting the Breaker Failure function is provided with a BF1 INITIATE submenu.
INITIATE IN1 (to IN15)
Range: Off, Any FlexLogic operand
Default: Ph TOC 1 OP
The setpoint selects the FlexLogic operand that initiates the Breaker Failure scheme;
typically the trip signals from internal protection functions.
The default setting includes the following protection functions:
Ph TOC 1 OP
Ph TOC 2 OP
Ph IOC 1 OP
Ph IOC 2 OP
Ntrl TOC 1 OP
Ntrl TOC 2 OP
Ntrl IOC 1 OP
Ntrl IOC 2 OP
GND TOC 1 OP
GND IOC 1 OP
Setpoints.
CONTROL
4–371