Toshiba MMU-AP0072H2UL-1 Service Manual page 67

Hide thumbs Also See for MMU-AP0072H2UL-1:
Table of Contents

Advertisement

Address setup (Manual setting from Wired remote control)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote control.
• Turn on power supply.
1
CL
Push
SET
+
+
TEST
for 4 seconds or more.
2
(Line address)
Using the temperature setup
12 12 12 12 12
buttons, set
to the CODE No.
3
Using timer time
set the line address.
4
Push
button. (OK when display goes on.)
SET
5
(Indoor unit address)
Using the temperature setup
13 13 13 13 13
buttons, set
to the CODE No.
6
Using timer time
set 1 to the line address.
7
Push
button. (OK when display goes on.)
SET
8
(Group address)
Using the temperature setup
14 14 14 14 14
buttons, set
to the CODE No.
9
Using timer time
0000
0000
0000
0000
0000
set
to Individual,
0002
0002
0002
0002
0002
Header unit and
10
Push
SET
button.
(OK when display goes on.)
11
Push
button.
TEST
Setup completes.
(The status returns to the usual stop status.)
Note 1)
When setting the line address from the remote control, do not use Address 29 and 30.
As they are addresses which cannot be set to the outdoor unit, if they are set, the check code [E04] (Indoor/Outdoor
communication circuit trouble) is issued.
Note 2)
When an address was manually set from the remote control and the central control over the refrigerant lines is
carried out, perform the following setting for the Header unit of each line.
• Set the line address for every line using SW13 and 14 on the interface P.C. board of the Header unit in each line.
• Except the least line address No., turn off SW30-2 on the interface P.C. board of the Header units in the lines
connected to the identical central control.
(Draw the terminal resistances of indoor/outdoor and central control line wirings together.)
• For each refrigerant line, connect the relay connector between Header unit [U1U2] and [U3U4] terminals.
• After then set the central control address.
(For setting of the central control address, refer to the Installation manual for the central control equipment.)
buttons simultaneously
/
/
buttons,
/
/
buttons,
/
/
buttons,
0001
0001
0001
0001
0001
to
to follower unit.
(Example of 2-lines cabling)
(Real line: Wiring, Broken line: Refrigerant pipe)
Outdoor
Indoor
Line address → 1
Indoor unit address → 1
Group address → 1
Header unit
For the above example, perform setting by connecting singly the
wired remote control without remote control inter-unit cable.
Group address
Individual
Header unit
Follower unit : 0002
TEMP.
2, 5, 8
11
END
FILTER
RESET
TEST
1
<Operation procedure>
1
2
7
8
67
Outdoor
Indoor
Indoor
Indoor
1
1
2
2
3
1
2
2
2
Follower
unit
: 0000
: 0001
In case of group control
ON / OFF
3, 6, 9
TIMER SET
FAN
MODE
TIME
SAVE
VENT
4, 7, 10
SET
CL
SWING/FIX
UNIT LOUVER
3
4
5
9
10
11
Indoor
2
2
2
6
END

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents