Issue 08/03
NOTE
rd
The 3
type of parameter is a "bit" parameter. For further information on this, see the operating
instructions.
NOTE
The BOP sometimes display
presently handling another higher priority task.

5.2 Factory Reset

START
User access level
P0003 = 1
Commissioning parameter
P0010 = 30
Factory reset
P0970 = 1
The drive carries-out a parameter reset (duration, approx. 60s) and
then automatically exits the reset menu and sets
P0970
NOTE
When resetting the parameters to the factory setting, the communications memory is re-initialized.
This means that communications via USS in addition to the PROFIBUS / DeviceNet / CanBus CB
board are interrupted during the reset:
The "busy" text is displayed on the BOP during the parameter reset.
After reset has been completed, communications are automatically re-established when using
STARTER, DriveMonitor or the BOP.
5.3

Commissioning an MM440

In quick commissioning you set all of the basic parameters necessary to get your motor turning. The
user must obtain all motor data information from the name plate on the motor before beginning this
process.
Here is some information about how to read the parameter data from the name plate:
44
when changing parameter values. This means that the drive is
1 :
Access level, standard
30 :
Factory setting
1 :
Parameter reset to the default values
P0970 = 0 :
Disabled
P0010 = 0 :
Ready
Quick Start Guide
MICROMASTER 440
6SE6400-5GA00-0BP0