Without Hym - Trane CGAX/CXAX Manual

Scroll compressor 42-160 kw
Table of Contents

Advertisement

Table 8 - CXAX High Effi ciency and Low Noise (continued)
Eurovent Performances (1)
Net Cooling Capacity
Total Power input in cooling
EER
ESEER
Eurovent Effi ciency class Cooling
Sound power level
Heating application data (2)
Net Heating Capacity
Total Power input in heating
COP
Eurovent Effi ciency class Heating
ηs
SCOP
Unit amps (4) (5)
Unit rated amps
Unit rated amps - HESP
Unit start up amps
Unit start up amps - HESP
Short Circuit Unit Capacity (9)
Compressor
Compressor Number per Circuit
Type
Model Circuit1 / Circuit 2
Rated Amps Circuit1 / Circuit 2 (4)
Locked Rotor Amps Circuit1 / Circuit 2 (4)
Motor RPM
Oil sump heater Circuit1 / Circuit 2
Evaporator
Quantity
Type
Evaporator model
Evaporator Water Content volume
Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm)
Nominal water connection size (Grooved coupling) - With HYM
Hydraulic Module Components
Expansion Tank Volume
Max User water loop Volume for factory mounted expansion tank (1)
Optional water Buffer tank volume
Max. Water-side Operating Pressure without pump package
Max. Water-side Operating Pressure with pump package
Condenser
Type
Quantity of coil
Face area per circuit
Condenser Fan
Quantity
Diameter
Fan / motor Type
Airfl ow per Fan
Motor RPM
Partial Heat recovery (PHR) option
Heat-Exchanger Type
Heat-Exchanger Model
Water connection size (Thread connection)
Water content volume
Dimensions
Unit Length
Unit Width
Unit Height
Option Additional height
Water Buffer tank option
Weights
Shipping Weight (5)
Operating Weight (5)
Option Additional shipping weight
Single pump - Standard head pressure
Single pump - High head pressure
Twin pump - Standard head pressure
Twin pump - High head pressure
Partial heat recovery option
Water Buffer tank option
System data
Nb of refrigerant circuit
Minimum cooling load % (6)
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2
Oil charge Circuit1 / Circuit 2
Unit with partial heat receovery option
R410a refrigerant charge Circuit1 / Circuit 2
Oil charge Circuit1 / Circuit 2
POE Oil type
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C/6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.
CG-PRC026C-GB
CXAX
CXAX
015
017
HE-LN
HE-LN
(kW)
108
118
(kW)
36
41
3.00
2.88
4.20
4.02
B
C
(dBA)
81
82
(kW)
110
120
(kW)
35
39
3.14
3.12
B
B
(%)
133
132
3.39
3.37
(A)
86
98
(A)
86
98
(A)
218
224
(A)
218
224
(kA)
15
15
#
3
3
Scroll
Scroll
13+13+13
15+15+15
25.3+25.3+
29.5+29.5+
(A)
25.3
29.5
(A)
158+158 +158 155+155 +155
(rpm)
(W)
0.25 / 0
0.25 / 0
#
1
1
P120Tx110
P120Tx110
(l)
13.3
13.3
2" - 60.3
2" - 60.3
(in) - (mm)
3" OD - 76.1
3" OD - 76.1
(l)
35
35
(l)
2000
2000
(l)
444
444
(kPa)
(kPa)
#
2
2
(m²)
5.93
5.93
#
3
3
(mm)
(m
/h)
13823
13828
3
(rpm)
B3-027-20-4.5L
B3-027-20-4.5L 2x B3-014-14-4.5M 2x B3-014-14-4.5M 2x B3-014-14-4.5M 2x B3-027-14-4.5L 2x B3-027-14-4.5L
G 1"1/4
G 1"1/4
(in) - (mm)
(31.75 mm)
(31.75 mm)
(l)
0.5
0.5
(mm)
2327
2327
(mm)
2250
2250
(mm)
1747
1747
(mm)
+330
+330
(kg)
954
972
(kg)
925
942
(kg)
47
47
(kg)
49
49
(kg)
75
75
(kg)
86
86
(kg)
4.6
4.6
(kg)
425
425
#
1
1
%
33
33
(kg)
26.0
26.0
(l)
10.5
11.5
(kg)
26.0
26.0
(l)
10.5
11.5
CXAX
CXAX
CXAX
020
023
026
HE-LN
HE-LN
HE-LN
94
114
127
34
37
43
2.81
3.06
2.96
3.98
4.10
4.00
C
B
B
81
84
83
101
114
127
32
37
42
3.16
3.08
3.02
B
B
B
131
124
124
3.35
3.16
3.16
78
93
104
78
93
104
200
215
236
200
215
236
15
15
15
2
2
2
Scroll
Scroll
Scroll
7.5+10 /
10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
7.5+10
15.5 / 20.2 /
20.2 / 20.2 /
20.2 / 25.3 /
15.5+20.2
20.2+20.2
20.2+25.3
98 / 142 /
142 / 142 /
142 / 158 /
98+142
142+142
142+158
2900
0.17 / 0.17
0.17 / 0.17
0.17 / 0.17
1
1
1
Stainless steel Copper Brazed plate Heat exchanger
DP300x82
DP300x82
DP300x82
8.5
8.5
8.5
3" OD - 76.1
3" OD - 76.1
3" OD - 76.1
3" OD - 76.1
3" OD - 76.1
3" OD - 76.1
35
35
35
2000
2000
2000
444
444
444
1000
400
Aluminum fi ns & copper tubes heat exchanger
2
2
2
2.96
2.96
2.96
2
4
4
800
Propeller fan : Variable speed - EC motor
14960
14964
12725
150 - 686 RPM
Stainless steel Copper Brazed plate Heat exchanger
G 1"1/4
G 1"1/4
G 1"1/4
(31.75 mm)
(31.75 mm)
(31.75 mm)
2x0.14
2x0.14
2x0.14
2327
2327
2327
2250
2250
2250
1747
1747
1747
+330
+330
+330
1000
1098
1098
974
1072
1072
45
47
47
49
49
49
75
75
75
84
84
84
2x1.48
2x1.48
2x1.48
425
425
425
2
2
2
22
25
22
13.0 / 13.0
13.5 / 13.5
13.0 / 13.0
6.3 / 6.3
6.6 / 6.6
6.6 / 6.6
13.0 / 13.0
13.5 / 13.5
13.0 / 13.0
6.3 / 6.3
6.6 / 6.6
6.6 / 6.6
OIL058E / OIL057E
General Data
CXAX
CXAX
030
036
HE-LN
HE-LN
146
162
49
55
2.95
2.93
4.03
3.95
B
B
83
84
139
162
46
52
3.00
3.11
B
B
128
129
3.28
3.30
114
131
114
131
247
256
247
256
15
15
2
2
Scroll
Scroll
25.3 / 25.3 /
29.5 / 29.5 /
25.3+25.3
29.5+29.5
158 / 158 /
155 / 155 /
158+158
155+155
0.17 / 0.17
0.17 / 0.17
1
1
DP300x114
DP300x114
11.8
11.8
3" OD - 76.1
3" OD - 76.1
3" OD - 76.1
3" OD - 76.1
35
35
2000
2000
444
444
2
2
2.96
3.46
4
4
12725
13351
G 1"1/4
G 1"1/4
(31.75 mm)
(31.75 mm)
2x0.35
2x0.35
2327
2327
2250
2250
1747
1947
+330
+330
1120
1190
1093
1163
47
47
49
49
75
75
84
84
2x3.82
2x3.82
425
425
2
2
25
25
13.5 / 13.5
14.5 / 14.5
6.6 / 6.6
7.2 / 7.2
13.5 / 13.5
14.5 / 14.5
6.6 / 6.6
7.2 / 7.2
29

Advertisement

Table of Contents