ABB ACH550-01 User Manual page 185

Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

Code Description
0305 FAULT WORD 1
Read-only copy of the Fault Word 1
• When a fault is active, the corresponding bit for the active fault is set
in the Fault Words.
• Each fault has a dedicated bit allocated within Fault Words.
• See
Fault listing
• The control panel displays the word in hex. For example, all zeros
and a 1 in Bit 0 display 0001. All zeros and a 1 in Bit 15 display 8000.
Bit # 0305,
FAULT WORD
0
OVERCURRENT
1
DC OVERVOLT
2
DEV OVERTEMP
3
SHORT CIRC
4
Reserved
5
DC UNDERVOLT
6
AI1 LOSS
7
AI2 LOSS
8
MOT OVERTEMP
9
PANEL LOSS
10
ID RUN FAIL
11
MOTOR STALL
12
CB OVERTEMP
13
EXT FAULT 1
14
EXT FAULT 2
15
EARTH FAULT
0306 FAULT WORD 2
Read-only copy of the Fault Word 2
• See parameter 0305.
0307 FAULT WORD 3
Read-only copy of the Fault Word 3
• See parameter 0305.
180
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
on page
371
for a description of the faults.
1 0306,
FAULT WORD
Obsolete
THERM FAIL
OPEX LINK
OPEX PWR
CURR MEAS
SUPPLY PHASE
Reserved
OVERSPEED
Reserved
DRIVE ID
CONFIG FILE
SERIAL 1 ERR
EFB CON FILE
FORCE TRIP
MOTOR PHASE
OUTP WIRING
Parameter listing and descriptions
ACH550-01 User's Manual
Range
-
2 0307,
FAULT WORD
EFB 1
EFB 2
EFB 3
INCOMPATIBLE SW
USER LOAD CURVE
Reserved
Reserved
Reserved
Reserved
Reserved
System error
System error
System error
System error
System error
Param. setting fault
-
-
3