Mitsubishi MXZ-2D33VA Service Manual page 151

Outdoor unit
Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

• The cooling operation or the heating operation does not operate.
Check of R.V. coil
MXZ-2D33VA/2D40VA/2D42VA/2D42VA2/2D53VA/2D53VA2
MXZ-2D53VAH/2D53VAH2
• The heating operation does not operate.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 230 V AC between pin1 and
pin2 at connector CN721?
Yes
Turn OFF the power supply. Disconnect the connector CN721.
Is there normal resistance
to R.V. coil?
(Refer to 11-5.)
Yes
Replace the 4-way valve.
• The cooling operation does not operate.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 230 V AC between pin1 and
pin2 at connector CN721?
No
Replace the 4-way valve.
OBH626L
No
No
Replace the R.V. coil.
Yes
Replace the inverter P.C. board.
Replace the inverter P.C. board.
151
MXZ-2D
CN721
Inverter P.C. board