3.2 Installation of the PBX
3.2.13 Surge Protector Installation
Overview
A massive electrical surge can be caused if lightning strikes a telephone cable 10 m (33 ft) above ground,
or if a telephone line comes into contact with a power line. A surge protector is a device that is connected
to a CO line to prevent potentially dangerous electrical surges from entering the building via the CO line and
damaging the PBX and connected equipment.
To protect the system from electrical surges, we strongly recommend connecting the system to a surge
protector that meets the following specifications:
–
Surge arrestor type: 3-electrode arrestor
–
DC spark-over voltage: 230 V
–
Maximum peak current: at least 10 kA
Additionally, proper grounding is very important for the protection of the system (refer to "3.2.5 Frame ground
Connection").
Many countries/areas have regulations requiring surge protection. Be sure to comply with all applicable
laws, regulations, and guidelines.
Installation
CO Line
Surge
Protector
Ground
76
Installation Manual
CO Line
CO Line
Terminal
Board
Extn.
SLT
PT
CS
PT-interface CS
Extn.
PBX
Frame
Ground
Extn.: Extension line