To address a ZS duct sensor

Each ZS Sensor on an Rnet must have a unique address, but addresses do not have to be sequential.
Open the hinged cover on the sensor enclosure, and then use the DIP switches to set an address from 0 to 14. (1
is factory default.) Each DIP switch has the value shown in the figure below. Turn on as many DIP switches as you
need so that their total value equals the address.
DIP
Switch
value
1
2
4
8

To mount a ZS duct temperature or temperature/humidity sensor

Temperature sensor
ZS Sensors
Installation Guide
EXAMPLE DIP switches 1 and 4 above
are on. Their values (1 + 8) total 9, so
the sensor's address is 9.