Cisco 12012 Replacement Instructions Manual page 4

Gigabit switch router dc-input power supply
Table of Contents

Advertisement

Product Overview
The source DC power cable leads and lugs from the source DC service circuit breaker to the power
supply must meet the following requirements:
Figure 3
End View
.55
DC-Input Power Supply LEDs
The faceplate of the DC-input power supply has two LEDs: a green input OK LED and a red output
fail LED. (Refer to Figure 4.)
Figure 4
4 Cisco 12012 Gigabit Switch Router DC-Input Power Supply Replacement Instructions
Three power cables—4 AWG (American Wiring Guide), 0.204-inch (5.18-mm) diameter, high
strand count. The cable length is dependent on your router location. This cable is not available
from Cisco Systems: it is available from any commercial cable vendor.
Three power lugs—Must be dual-hole with .625-inch (15.86-mm) centers and able to fit over M6
threaded terminals. (Refer to Figure 3.) This type of lug is not available from Cisco Systems;
electrical-connector vendors, such as Panduit, provide this type of lug.
Source DC Power Cable Lug
Ø .267
2 holes
.25
.08
DC-Input Power Supply LEDs
DC-input power supply
2.25
Crimp area
.63
.37
INPUT OK
LED
OUTPUT FAIL
LED
All measurements in inches
4 AWG conductor