GE 339 Instruction Manual page 282

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

S5 INPUTS/OUTPUTS
Output Relay 1 "Breaker Trip" - Input/Output "E"
6–148
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to Chapter 3 - Working with the Keypad.
PATH:
SETPOINTS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS > RLY 1 TRIP
SEAL IN TIME
Range: 0.00 to 9.99 s in steps of 0.01
Default: 0.04 s
This setting defines the time to be added to the reset time of the Relay 1 Trip output,
thus extending its pulse width. This is useful for those applications where the 52 contacts
reporting the breaker state are faster than the 52 contacts that are responsible for
interrupting the coil current.
BLOCK RLY 1 TRIP
For details see
Common
This setting defines a block to the Trip Output relay. When the selected input is asserted,
the Trip Output relay will be blocked.
setpoints.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS

Advertisement

Table of Contents
loading

Table of Contents