6. Technical data

Operating voltage
Frequency
Standby
Switching capacity max.
Switching capacity
Switching capacity min.
Protection rating
Protection class
Operating temperature
Shortest switching time
Power reserve
Time accuracy (typical)
Contact material
Rated impulse voltage
Pollution degree
Contact
Max. switching cycles with 16 A resistive
load
Incandescent lamp load
Halogen lamp load
Fluorescent lamps (LLB low-loss
ballasts):
uncompensated
series compensated
parallel compensated
Fluorescent lamps (EB – Electronic
Ballasts):
Mercury and sodium vapour lamps
parallel-compensated
Compact fluorescent lamps (EB)
LED lamps (< 2 W)
LED lamps (2 W – 8 W)
LED lamps (> 8 W)
Corresponds to type 1 STU in accordance
with IEC/EN 60730-2-7 or IEC/
EN 60730-1
Switching of SELV is only permitted with
171011, not with 1720100
7. Contact
Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Phone +49 7474 692-0
Fax +49 7474 692-150
Hotline
Phone +49 7474 692-369
hotline@theben.de
Addresses, telephone numbers etc.
www.theben.de
230–240 V AC +10 % / –15 %
50-60 Hz
1.4 W (1710100)
0.8 W (1720100)
16 A (at 250 V AC, cos ϕ = 1)
10 A (at 250 V AC, cos ϕ = 0.6)
10 mA/230 V AC
100 mA/12 V AC/DC
IP 20 in accordance with EN
60529
II in accordance with EN
60730-1 subject to designated
installation
–30 °C ... +55 °C
1 min.
10 years at +20 °C
± 0.25 s/day (25 °C)
AgSnO
2
4 kV
2
Changeover contact, µ contact
50 000
2600 W
2600 W
2300 VA
2300 VA
730 W (80 µF)
650 W
730 VA (80 µF)
170 W
30 W
100 W
120 W
8