Pqry-P72~336Y(S)Lmu-A Specifications - Mitsubishi Electric PQRY-P72TLMU-A Manual

Table of Contents

Advertisement

1. SPECIFICATIONS

1-2. PQRY-P72~336Y(S)LMU-A Specifications

Model
Power source
Cooling capacity (Nominal) *1 (460V)
Power input
Current input
Indoor
Temp. range
of cooling
Circulating water *3
(460V)
Heating capacity (Nominal) *2
Power input
Current input
Indoor
Temp. range
of heating
Circulating water *3
Indoor unit
Total capacity
connectable
Model / Quantity
Sound pressure level (measured in anechoic
room)
Refrigerant
High pressure
piping
Low pressure
diameter
External finish
External dimension HxWxD
Net weight
Type
Water volume in plate
Heat
exchanger
Water pressure Max.
Type
Manufacturer
Starting method
Compressor
Motor output
Lubricant
Water flow rate
Circulating
water *3
Pressure drop
Operating volume range
High pressure protection
Protection
Inverter circuit(comp)
devices
Compressor
Minimum Circuit Ampacity(MCA)
Maximum Overcurrent Protection(MOP)
Type x original charge
Refrigerant
Control
External
Drawing
Wiring
Document
Standard
attachment
Accessory
Optional parts
Remarks
Note:
*1 Nominal cooling conditions (subject to JIS B8615-1)
Indoor:
81degF D.B./ 66degF W.B. (27degC D.B./ 19degC W.B.) 68degF D.B. (20degC D.B.)
Water Temp.:
86degF (30degC)
Pipe length:
24-9/16ft.(7.5m)
Level difference:
0ft.(0m)
* Due to continuing improvement, above specifications may be subject to change without notice.
© 2017 Mitsubishi Electric US, Inc.
PQRY-P72YLMU-A
3-phase 3-wire 460 ±10% 60Hz
Btu/h
72,000
kW
21.1
kW
3.23
A
4.5
W.B.
59~75° F (15~24° C)
50~113° F (10~45° C)
Btu/h
80,000
kW
23.4
kW
3.63
A
5
D.B.
59~81° F (15~27° C)
50~113° F (10~45° C)
50~150% of heat source unit capacity
P06~P96/1~18
dB <A>
46
in.(mm)
5/8 (15.88) Brazed
in.(mm)
3/4 (19.05) Brazed
Galvanized steel sheets
in.
43-5/16 x 34-11/16 x 21-11/16
mm
1,100 x 880 x 550
lbs(kg)
404 (183)
Plate
G
1.32
I
5
psi
290
MPa
2
Inverter scroll hermetic compressor
Inverter
kW
4.3
MEL32
G/h
1,522
G/min(gpm)
25.4
m
/ h
5.76
3
L/min
96
cfm
3.4
psi
3.48
kPa
24
G/h
793 ~ 1,902
G/min(gpm)
13.2 ~ 31.7
m
/ h
3.0 ~ 7.2
3
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection
Over-heat protection
A
6
A
15
R410A x 11 lbs + 1 oz (5.0 kg)
Indoor LEV and BC controller
KJ94T129
KE94C952
Installation Manual
Details refer to External Drw
BC controller: CMB-P104, 105, 106, 108, 1010, 1013, 1016NU-G1
Main BC controller: CMB-P108, 1010, 1013, 1016NU-GA1, 108, 1010, 1016NU-HA1
Sub BC controller: CMB-P104, 108NU-GB1, CMB-P1016NU-HB1
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
The ambient temperature of the Heat Source Unit needs to be kept below 104°F DB(40° C DB).
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
A field provided flow switch is required for minimum flow protection on each module, field installed and wired to
TB8 (terminal 3-4).
*3 If using Circulating water temperatures that are between 23 and 50° F, Dip switch 3-9 must be turned
on and glycol must be used in the water loop to prevent freezing down to 5° F.
*2 Nominal heating conditions (subject to JIS B8615-1)
68degF (20degC)
25ft.(7.6m)
0ft.(0m)
PQRY-P-T(S)LMU, Y(S)LMU (April 2017 Ver2)
50~150% of heat source unit capacity
Inverter scroll hermetic compressor
AC&R Works, MITSUBISH ELECTRIC CORPORATION
Over-heat protection, Over-current protection
Joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-R160-J1
Unit converter
BTU/h =kW x 3,412
cfm =m
lb =kg / 0.4536
* Above specification data is subject to rounding
variation.
PQRY-P96YLMU-A
3-phase 3-wire 460 ±10% 60Hz
96,000
28.1
4.65
6.4
59~75° F (15~24° C)
50~113° F (10~45° C)
108,000
31.7
5.05
7
59~81° F (15~27° C)
50~113° F (10~45° C)
P06~P96/1~24
48
3/4 (19.05) Brazed
7/8 (22.2) Brazed
Galvanized steel sheets
43-5/16 x 34-11/16 x 21-11/16
1,100 x 880 x 550
404 (183)
Plate
1.32
5
290
2
Inverter
6.0
MEL32
1,522
25.4
5.76
96
3.4
3.48
24
793 ~ 1,902
13.2 ~ 31.7
3.0 ~ 7.2
Over-heat protection
9
15
R410A x 11 lbs + 1 oz (5.0 kg)
Indoor LEV and BC controller
KJ94T129
KE94C952
Installation Manual
Details refer to External Drw
/min x 35.31
3
WR2-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents