Toshiba TOSVERT VF-S15 Manual page 23

Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

4.1.3.
Communication parameters for VF-S15/AS3
Communi
Title
cation No.
c081-
C081-
Device Name 1-16 (*1)
c096
C096
c100
C100
Inverter operation at the
c101
C101
communication loss action
Preset speed operation
c102
C102
selection
Communication error condition
c103
C103
selection
c154
C154
PROFIdrive JOG1 frequency
c155
C155
PROFIdrive JOG2 frequency
c156
C156
PROFIdrive Tmax
c157
C157
PROFIdrive Tolerance
c504
C504
IP mode (*2)
c505-
C505-
IP address setting value (*2)
c508
C508
c509-
C509-
Subnet mask setting value (*2)
c512
C512
c513-
C513-
Default gateway setting
c516
value (*2)
C516
c554
C554
Web server (*2)
(*1): (typ) does not work for this parameter.
(*2): These parameters are affected after reset.
Function
Communication error detection
delay time
Description
Max 16 characters
The device name is required if the card uses
DHCP to obtain its IP Address.
0.0 - 100.0 sec.
The waiting time of network error detection can be
adjusted. If a network error continues past the time
set in c100, it is recognized as a communication
error, and inverter will operate according the setting
of c101. If network error was removed during
c100, inverter will continue normal operation.
0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)
0: None
1 to 15: Preset speed
The operation frequency when the communication
fault is occurred can be selected from preset
speed. (Only when c101 is set to 5)
0: Always
1: Communication command (Frequency
reference and command from communication
option) enabled
2: 1+during run
0.0 to 20.0Hz
0.0 to 20.0Hz
0.1 to 60.0s
0.1 to 99.0%
Use this parameter to select the IP address
assignment method.
0: Manual
1:Invalid setting
2: DHCP
3: DCP
The IP address of the option module.
These fields are effective settings at c504 = 0.
The subnet mask of the option module.
These fields are effective settings at c504 = 0.
The gateway IP address of the option module.
These fields are effective settings at c504 = 0.
Enables web server.
0: Disable
1: Enable
- 20 -
E6582051
Default
setting
0
0.0
4
0
1
5.0Hz
5.0Hz
10.0s
50.0%
0
0.0.0.0
0.0.0.0
0.0.0.0
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tosvert vf-as3

Table of Contents