Outdoor Termination Kits And Corresponding Equivalencies; Vent Pipe Sizing Worksheet - Lennox G71MPP-36B-070 Installation Instructions Manual

G71mpp series units
Hide thumbs Also See for G71MPP-36B-070:
Table of Contents

Advertisement

TABLE
5
OUTDOOR
TERMINATION
KITS AND CORRESPONDING
EQUIVALENCIES
Vent Pipe Length Equivalency (feet)
Outdoor
Ex-
Outdoor
Ex-
VENT
haust Accel-
haust
Accel-
1-112"
2" Con-
3" Con-
2" Wall Plate
3" Wall
2" Wall
UNIT
PIPE
erator
erator
Concentric
centric
Kit
centric
Kit
Kit
Plate
Kit
Ring
Kit
MODEL
DIA.
(Dia. X
(Dia. X
Kit
(in.)
Length)
Length)
22G44
44J40
1-1/2" X 12"
2"X
12"
71M80
69M29
60L46
30G28
81J20
15F74
2
4
Not
12
Not
Not
4
4*
4
Allowed
Allowed
Allowed
2-1/2
5
Not
15
Not
Not
5
5*
5
Allowed
Allowed
Allowed
36B-070
3
8
Not
24
Not
Not
8
8*
8
Allowed
Allowed
Allowed
4
14
Not
42
Not
Not
14
14"
14
Allowed
Allowed
Allowed
2
Not
1
Not
3
3
Not
1
1"*
Allowed
Allowed
Allowed
2-1/2
Not
2
Not
6
6
Not
2
2**
Allowed
Allowed
Allowed
60C-090
3
Not
2
Not
6
6
Not
2
2**
Allowed
Allowed
Allowed
4
Not
4
Not
12
12
Not
4
4**
Allowed
Allowed
Allowed
2-1/2
Not
2
Not
6
6
Not
2
2
Allowed
Allowed
Allowed
60C-110
3
Not
2
Not
6
6
Not
2
2
Allowed
Allowed
Allowed
4
Not
4
Not
12
12
Not
4
4
Allowed
Allowed
Allowed
Not
3
Not
6
Not
Not
15
Not
6
Allowed
Allowed
Allowed
Allowed
Allowed
60D-135
4
Not
10
Not
Allowed
Allowed
*Requires
field-provided
and installed
1-1/2" exhaust
accelerator.
Not
Not
25
Not
10
Allowed
Allowed
Allowed
**Requires
field-provided
and installed
2" exhaust
accelerator.
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Proposed
vent pipe size :
Termination
kit catalog
number
:
Vent pipe equivalency
value from table 5 :
Total number
of 90 ° elbows
required
(indoors
and outdoors)
X 5 =
equivalent
feet of pipe
Total number
of 45 ° elbows
required
(indoors
and outdoors)
X 2.5 =
equivalent
feet of pipe
Linear feet of straight
pipe required
:
Add equivalent
feet of vent pipe listed in
steps 2 through
5.
Equivalent
Feet
TOTAL
If the total is equal to, or less than, the allowable
maximum
given
in table 7, the proposed
pipe size is acceptable.
If the
total exceeds
the maximum
allowed
vent pipe length,
repeat the process
above
using the next larger diameter
pipe until
an acceptable
total is achieved.
NOTE
- In Direct Vent systems,
total the equivalent
length of either the exhaust
OR intake piping run, depending
upon which
will be LONGER.
Intake and exhaust
pipe diameter
must be the same size and must be terminated
in the same pressure
zone. Intake
and exhaust
pipe should
be roughly
the same
length.
Page 14