Horizontal
Applications
The G71MPP furnace can be installed in horizontal ap-
plications with either right- or left-hand air discharge,
The G71MPP may also be installed as a unit heater. Either
suspend the furnace as shown in figure 14, or install the fur-
nace on a field-fabricated raised platform. The unit must be
supported at both ends and beneath the blower deck to
prevent sagging,
Refer to figure 13 for clearances in horizontal applications,
Horizontal Application
Installation Clearances
Left End
Air
Flow
Right-Hand Discharge
Top
) /
Right End
_
Air
Flow
Bottom
(Floor)**
Left End
Air
Flow
Left-Hand Discharge
Top
Bottom (Floor)**
Right
End
Air
Flow
Top
6
Front*
6
Back
6
Ends
6
Vent
6
Floor
65
*Front
clearance in alcove
installation
must be 24 in. (610 ram).
Maintain a minimum of 24 in. (610 ram) for front service access.
**A 5-1/2" service clearance must be maintained below the unit to
provide for servicing of the condensate
trap.
:_For installations
on a combustible
floor, do not install the fur-
nace directly on carpeting, tile or other combustible materials oth-
er than wood flooring.
FIGURE 13
Suspended Installation of Horizontal Unit
NOTE- If unit is suspended, horizontal support kit (Cat No.
56J18 ordered separately) or equivalent is recommended
to ensure proper unit support and coil drainage.
1 - Select location for unit keeping in mind service and
other necessary clearances. See figure 13,
2 - Provide service platform in front of unit,
3 - If unit is installed above finished space, fabricate a
drain pan fitted with a 1/2 inch or 3/4 inch N,P,T, fitting,
4 - Using 3/8 inch rods and support frame kit or field-fabri-
cated supports, fabricate suspension hangers, keep-
ing in mind front service access clearances.
5 - Mount unit on support frame as shown in figure 14,
6- Continue with exhaust, condensate
and intake line
piping instructions,
TYPICAL HORIZONTAL
APPLICATION
BLOWER ACCESS
3/8 in. RODS
PANEL
l
CONNECTION
©
_
_
_
2-
DRAIN PAN
SUPPORT FRAME
(to protect
finished space)
FIGURE 14
If unit is suspended above finished space, hang the
field-provided
drain pan below the support frame as
shown in figure 14. Leave 5-1/2 inches for service
clearance below unit for condensate trap,
Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner, If
necessary, run the condensate line into a condensate
pump to meet drain line slope requirements,
The
pump must be rated for use with condensing furnaces,
Protect the condensate discharge line from the pump
to the outside to avoid freezing.
Platform
Installation
of Horizontal
Unit
Select location for unit keeping in mind service and
other necessary clearances, See figure 13,
Construct a raised wooden frame and cover frame
with a plywood sheet, Provide a service platform in
front of unit, If unit is installed above finished space,
fabricate a drain pan to be installed under unit.
When installing the unit in a crawl space, a proper sup-
port platform may be created using cement blocks and
the horizontal support frame kit (ordered separately,
Page 11