3 Design and Installation of the 810D
3.2 Installing the SINUMERIK 810D
3.2
Installing the SINUMERIK 810D
Preparation
For assembling the SINUMERIK 810D control, you need the following tools:
S
S
Position in the
The CCU box must be mounted to the right of the SIMODRIVE mains supply
overall installation
module.
With the CCU3, a further power module can be mounted to the left of the box.
Installing the
The CCU box is mounted to the right of the mains supply. The use of four M5
screws is recommended for fastening.
CCU box
1. Remove the plastic cover above the DC link busbars by loosening it with a
2. Use two M4 Torx screws to join the DC link busbars of the MS unit and the
3. Place the cover with the plastic lugs at the base of the corresponding
3-42
Screwdriver for slotted screws size 0 and 1
Screwdriver for M4 and M5 Torx screws.
screwdriver at the top and tilting it downwards and forwards.
CCU box and if applicable, the next module.
Check that all the screws connecting the DC links are tight.
cut-outs and close the DC link busbars by snapping the cover back until the
latch on the top snaps into place.
SINUMERIK 810D Manual Hardware Configuration (PHC) - - 11.02 Edition
E Siemens AG, 2002. All rights reserved
03.02