Installation Process; Outside Units Information - LG ARWB200LAS4 Installation Manual

Table of Contents

Advertisement

4

INSTALLATION PROCESS

Indicate clearly who will be responsible for switch setting.
Determination of division work
Make connection clearly between outside, indoor,
Preparation of contract drawings
remote controller and option.
Take account of gradient
Sleeve and insert work
of drain piping
Check model name to
Installation of indoor unit
make sure the fitting
is made correctly
Special attention to dryness,
Refrigerant piping work
cleanness and tightness
Drain pipe work
Adjust to downward gradient
Make sure airflow is sufficient
Duct work
Make sure no gaps are left where
Heat insulation work
the insulating materials are joined
Electrical work
Multiple core cable must not be used.
(connection circuits and drive circuits)
(suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
Airtight test
must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least
Vacuum drying
5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the
Additional charge of refrigerant
amount of added refrigerant
Make sure there are no gaps left between the facing materials
Fit facing panels
used on the ceiling
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work
Test run adjustment
has been fitted correctly
Explain the use of the system as clearly as possible to your customer and
Transfer to customer with explanation
make sure all relevant documentation is in order
!
CAUTION
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied
where local conditions warrants such change.
• The thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.(If the refrigerant
is charged in its gaseous state, its composition changes and the
system will not work properly.)

OUTSIDE UNITS INFORMATION

!
CAUTION
• Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each indoor unit capacity.
Combination Ratio(50~200%)
Outside Unit Number
Single outside unit s
Double outside unit s
More than Triple outside unit s
Notes: * We can guarantee the operation only within 130% Combina-
tion. If you want to connect more than 130% combination,
please contact us and discuss the requirement like below.
• If the operation of indoor unit is more than 130%, low airflow
operation is recommended in all the indoor units.
• If the operation of indoor unit is more than 130%, additional re-
frigerant is needed according to the Aheadquarter guidance.
• Over 130%, capacity is same as capacity of 130%, Same re-
mark is valid for power input.
Outside unit foundation work
The foundation must be level even
Installation of outside unit
Avoid short circuits and ensure
sufficient space is allowed for service
2
) there
Connection Ratio
200%
160%
130%
Power Supply : 3Ø, 380V, 60Hz or 3Ø, 380 - 415V, 50Hz
Model Name : ARWB***LAS4
Unit
System Capacity (HP)
8
Combination Unit
ARWB080LAS4
Model
Independent Unit
ARWB080LAS4
Refrigerant Precharged Amount
kg
5.8
Maximum Connectable Number of Indoor Units
13
kg
127 x 1
Net Weight
lbs
280 x 1
mm
755 × 997 × 500
Dimensions(WxHxD)
inch
(29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1
Liquid Pipes mm(inch)
9.52(3/8)
Low Pressure
mm(inch)
22.7(7/8)
Refrigerant
Gas Pipes
Connecting Pipes
High Pressure
mm(inch)
19.05(3/4)
Gas Pipes
Inlet
mm
PT40(Internal thread)
Water Connect-
Outlet
mm
PT40(Internal thread)
ing Pipes
Drain Outlet
mm
PT20(External thread) PT20(External thread) PT20(External thread)
Cooling
10°C ~ 45°C(50°F ~ 113°F)
Temp. range of
Circulation water
Heating
-5°C ~ 45°C(23°F ~ 113°F)
Unit
System Capacity (HP)
Combination Unit
ARWB140LAS4
Model
ARWB140LAS4
Independent Unit
Refrigerant Precharged Amount
kg
Maximum Connectable Number of Indoor Units
kg
127 x 1
Net Weight
280 x 1
lbs
755 × 997 × 500
mm
Dimensions(WxHxD)
(29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1
inch
12.7(1/2)
Liquid Pipes mm(inch)
Low Pressure
mm(inch)
25.4(1)
Refrigerant
Gas Pipes
Connecting Pipes
High Pressure
mm(inch)
19.05(3/4)
Gas Pipes
PT40(Internal thread)
Inlet
mm
Water Connect-
Outlet
mm
PT40(Internal thread)
ing Pipes
Drain Outlet
mm
PT20(External thread)
10°C ~ 45°C(50°F ~ 113°F)
Temp. range of
Cooling
Circulation water
Heating
-5°C ~ 45°C(23°F ~ 113°F)
Unit
System Capacity (HP)
Combination Unit
ARWB180LAS4
Model
Independent Unit
ARWB180LAS4
Refrigerant Precharged Amount
kg
Maximum Connectable Number of Indoor Units
kg
140 x 1
Net Weight
lbs
309 x 1
mm
755 × 997 × 500
Dimensions(WxHxD)
inch
(29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1
Liquid Pipes mm(inch)
12.7(1/2)
Low Pressure
mm(inch)
Refrigerant
28.58(1-1/8)
Gas Pipes
Connecting Pipes
High Pressure
mm(inch)
19.05(3/4)
Gas Pipes
Inlet
mm
PT40(Internal thread)
Water Connect-
Outlet
mm
PT40(Internal thread)
ing Pipes
PT20(External thread)
Drain Outlet
mm
Cooling
10°C ~ 45°C(50°F ~ 113°F)
Temp. range of
Circulation water
-5°C ~ 45°C(23°F ~ 113°F)
Heating
Unit
System Capacity (HP)
22
Combination Unit
ARWB220LAS4
Model
ARWB120LAS4
Independent Unit
ARWB100LAS4
Refrigerant Precharged Amount
kg
5.8 + 5.8
Maximum Connectable Number of Indoor Units
35
127 x 2
kg
Net Weight
lbs
280 x 2
(755 × 997 × 500) x 2
mm
Dimensions(WxHxD)
inch
(29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2
19.05(3/4)
Liquid Pipes mm(inch)
Low Pressure
mm(inch)
Refrigerant
34.9(1-3/8)
Gas Pipes
Connecting Pipes
High Pressure
mm(inch)
28.58(1-1/8)
Gas Pipes
PT40(Internal thread)
Inlet
mm
Water Connect-
PT40(Internal thread)
Outlet
mm
ing Pipes
PT20(External thread) PT20(External thread) PT20(External thread)
Drain Outlet
mm
10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F)
Cooling
Temp. range of
-5°C ~ 45°C(23°F ~ 113°F) -5°C ~ 45°C(23°F ~ 113°F) -5°C ~ 45°C(23°F ~ 113°F)
Circulation water
Heating
1 Unit
10
12
ARWB100LAS4
ARWB120LAS4
ARWB100LAS4
ARWB120LAS4
5.8
5.8
16
20
127 x 1
127 x 1
280 x 1
280 x 1
755 × 997 × 500
755 × 997 × 500
9.52(3/8)
12.7(1/2)
22.7(7/8)
25.4(1)
19.05(3/4)
19.05(3/4)
PT40(Internal thread)
PT40(Internal thread)
PT40(Internal thread)
PT40(Internal thread)
10°C ~ 45°C(50°F ~ 113°F)
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
1 Unit
14
16
ARWB160LAS4
ARWB160LAS4
5.8
3
23
26
140 x 1
309 x 1
755 × 997 × 500
12.7(1/2)
28.58(1-1/8)
19.05(3/4)
PT40(Internal thread)
PT40(Internal thread)
PT20(External thread)
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
1 Unit
18
20
ARWB200LAS4
ARWB200LAS4
3
3
29
32
140 x 1
309 x 1
755 × 997 × 500
12.7(1/2)
28.58(1-1/8)
19.05(3/4)
PT40(Internal thread)
PT40(Internal thread)
PT20(External thread)
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
2 Unit
24
26
ARWB240LAS4
ARWB260LAS4
ARWB120LAS4
ARWB140LAS4
ARWB120LAS4
ARWB120LAS4
5.8 + 5.8
5.8 + 5.8
39
42
127 x 2
127 x 2
280 x 2
280 x 2
(755 × 997 × 500) x 2
(755 × 997 × 500) x 2
19.05(3/4)
19.05(3/4)
34.9(1-3/8)
34.9(1-3/8)
28.58(1-1/8)
28.58(1-1/8)
PT40(Internal thread)
PT40(Internal thread)
PT40(Internal thread)
PT40(Internal thread)