Maintenance and Upgrades
Figure 25: Tightening the Terminal Block Captive Screws
1
Step 6
Repeat these steps for the remaining DC input power source wire as applicable.
Step 7
Use a tie wrap so secure the wires to the rack, so that the wires are not pulled from the terminal block.
Step 8
Set the DC disconnect switch in the circuit to ON. In a system with multiple power supplies, connect each power supply
to a separate DC power source. In the event of a power source failure, if the second source is still available, it can maintain
system operation.
Step 9
Verify power supply operation by checking the power supply LED on the front of the chassis. See
on page 9
for the LED values.

Secure the Power Cord on the Power Supply Module

To secure the power supply module against accidental removal and thus prevent disrupting system performance,
use the tie wrap and clamp provided in the accessories kit that ships with your Firepower 2100 security
appliance.
Take note of the following warnings:
Negative (-) lead wire

Secure the Power Cord on the Power Supply Module

2
Positive (+) lead wire
Cisco Firepower 2100 Series Hardware Installation Guide
Front Panel LEDs,
51