HFC-410A CHARGING INFORMATION — FOR COMPLETE CHARGING DETAILS, REFER TO THE OUTDOOR UNIT INSTALLATION AND SERVICE PROCEDURE
Maintenance checks using the Normal Operating Pressures table
Table 2 may be used to help perform maintenance checks. This table is not a procedure for charg­
ing the system and any minor variations in the pressures may be expected due to differences in
installations. However, significant deviations could mean that the system is not properly charged
or that a problem exists with some component in the system.
Charge Using the Subcooling Method
Cooling Mode—When the outdoor ambient temperature is 60°F (15°C) and above, use the cool­
ing mode to adjust the charge using the subcooling method. Target subcooling values in table
1 are based on 70 to 80°F (21-27°C) indoor return air temperature.
Heating Mode—When the outdoor ambient temperature is below 60°F (15°C), use the heating
mode to adjust the charge using the subcooling charge levels (table ). Target subcooling values
in table 1 are based on 65-75°F (18-24°C) indoor return air temperature.
Matchups/Charge Levels and Line Set Lengths
Table 1 - Normal Operating Pressures (Liquid
Heating Mode
ºF (ºC)*
20
30
SIZE
VAP/LIQ
VAP/LIQ
VAP/LIQ
-018
65/289
80/304
-024
58/281
72/295
-030
55/274
69/286
-036
62/287
76/304
-042
58/293
73/335
-048
60/282
75/299
-060
56/266
70/285
*Temperature of the air entering the outside coil.
HP
Indoor Coil or Air
Heat
Size
Handler
(+5ºF)
CBX25UH-018
13
CBX25UHV-018
CBX27UH-018
8
CBX27UH-024
8
CBX32MV-018/024
9
CH33-25A
10
-018
CH33-25B
11
CR33-30/36
18
CX34-25
8
CX34-31
10
CBX25UH-024
6
CBX25UHV-024
CBX25UH-030
17
CBX25UHV-030
CBX26UH-024
17
CBX27UH-024
12
CBX27UH-030
11
CBX32M-018, -024
14
CBX32M-030
12
CBX32MV-018/024
14
CBX32MV-024/030
12
CBX32MV-036
11
-024
CBX40UHV-024
11
CBX40UHV-030
11
CH23-41
10
CH33-25A
20
CH33-25B
19
CH33-31A
15
CH33-36C
10
CH33-36A
20
CR33-30, -036
17
CX34-25
15
CX34-31
15
CX34-36
26
CX34-38
10
CBX25UH-030
9
CBX25UHV-030
CBX25UH-036
19
CBX26UH-030
19
CBX27UH-030
10
CBX27UH-036
10
CBX32M-030
7
CBX32M-036
10
CBX32MV-024/030
7
-030
CBX32MV-036
10
CBX40UHV-030
10
CBX40UHV-036
10
CH23-41
11
CH23-51
11
CH33-31A
16
CH33-31B
16
CH33-36A
10
The values in this table are most popular match-up pressures; indoor match-up, indoor air quantity, and indoor load will cause the pressures to vary. *Amount of charge required in addition to charge shown on unit
nameplate.
10 and Suction
+
40
50
60
65
VAP/LIQ
VAP/LIQ
VAP/LIQ
97/322
116/341
137/360
132/224
88/ 309
105/324
123/340
139/243
84/ 299
102/313
122/327
135/250
91/ 322
106/342
124/365
135/230
89/ 368
108/394
130/411
127/215
90/ 316
105/334
121/353
136/219
84/ 309
99/ 337
114/369
132/222
Table 2 - Indoor Unit Matches and Subcooling Charge Levels and Additional Charge
Additional
Subcool
HP
Charge
Cool
Size
lbs
oz
(+1ºF)
3
0
0
9
1
2
9
1
2
4
0
3
6
0
9
5
0
4
5
0
9
-030
4
0
9
7
0
8
6
0
9
3
0
15
3
0
15
12
1
2
11
2
1
11
0
4
12
1
2
11
0
4
12
1
2
11
2
1
11
2
1
11
2
1
3
0
0
10
1
1
8
1
2
-036
11
1
15
12
0
0
10
1
1
4
0
14
9
0
15
16
0
9
6
0
9
18
1
14
3
0
8
11
1
5
11
1
5
16
1
14
16
1
14
10
1
3
16
1
14
10
1
3
16
1
14
16
1
14
-042
16
1
14
4
0
8
6
0
14
18
2
8
18
2
6
6
0
6
Table 2 lists all the Lennox recommended indoor unit matchups along with the charge levels for
the various sizes of outdoor units. Charge levels on the unit nameplate are based on installa­
tions with 15' (4.6m) line sets; be sure to consider any difference in line set length (see
Installation Instructions for more details).
Charge Using the Weigh‐in Method
If the system is void of refrigerant, locate and repair any leaks and then weigh in the refrigerant
charge into the unit. For charge adjustments, be sure to consider line set length differences and,
referring to table 1, adjust for the matchup difference.
1 - Recover the refrigerant from the unit.
2 - Conduct leak check; evacuate as previously outlined.
3 - Weigh in the unit nameplate charge, adjusting for matchup and line set length differences.
If weighing facilities are not available use the Subcooling method.
5 psig)
+
70
75
80
VAP/LIQ
VAP/LIQ
VAP/LIQ
134/239
135/257
136/279
140/262
142/281
143/302
136/268
138/288
140/308
137/248
139/268
141/288
129/234
131/254
132/275
137/237
138/256
139/277
133/241
134/262
135/283
Subcool
Indoor Coil or Air
Cool
Heat
Handler
(+5ºF)
(+1ºF)
CH33-36B
6
3
CH33-36C
10
11
CH33-42B
16
18
CH33-43C
4
9
CR33-30, -36
22
5
CX34-31
17
15
CX34-36
25
6
CX34-38
10
19
CX34-42
25
6
CX34-43
13
17
CX34-44, -48
9
21
CBX25UH-036
31
3
CBX25UHV-036
CBX26UH-036
31
3
CBX27UH-036
18
3
CBX27UH-042
11
4
CBX27UH-048
11
4
CBX32M-036
18
3
CBX32M-042
18
3
CBX32MV-036
18
3
CBX32MV-048
11
4
CBX40UHV-042
11
4
CBX40UHV-048
11
4
CBX40UHV-036
18
3
CH33-43B
14
8
CH33-43C
26
9
CH33-44/48B
24
8
CH33-48C
26
9
CH33-49C
15
8
CH33-50/60C
15
8
CR33-48
38
5
CR33-50, -60
15
5
CX34-38
15
4
CX34-43
23
8
CX34-44/48
40
4
CX34-49
11
7
CX34-50/60
23
8
CBX25UH-042
42
5
CBX25UHV-042
CBX26UH-042
42
5
CBX27UH-042, -048
13
5
CBX32M-048
13
5
CBX32MV-048
13
5
CBX40UHV-042
13
5
CBX40UHV-048
13
5
CH23-68
20
9
CH33-43B
7
9
CH33-43C
22
5
CH33-44/48B
18
4
CH33-48C
22
5
Cooling Mode
85
90
95
100
VAP/LIQ
VAP/LIQ
VAP/LIQ
VAP/LIQ
138/300
138/322
140/344
141/369
144/325
145/348
145/373
146/399
141/330
143/352
144/376
145/400
143/311
145/334
146/359
148/385
134/298
136/321
137/346
139/371
140/298
141/321
142/344
143/369
137/306
138/330
139/354
141/380
Additional
HP
Indoor Coil or Air
Charge
Size
Handler
lbs
oz
0
0
CH33-49C
1
5
CH33-50, -60C
2
6
CH33-60D
1
12
CH33-62D
1
0
CR33-50, -60
2
10
CR33-60D
0
10
CX34-49
-042
2
14
CX34-50, -60
0
10
CX34-60
2
14
CX34-62C
2
12
CX34-62D
CBX25UH-048
0
4
CBX25UHV-048
0
4
CBX26UH-048
0
5
CBX27UH-048
0
1
CBX27UH-060
0
1
CBX32M-048
0
5
CBX32M-060
0
5
CBX32MV-048
0
5
CBX32MV-060
0
1
CBX32MV-068
0
1
CBX40UHV-048
0
1
CBX40UHV-060
-048
0
5
CH23-68
2
1
CH33-50, -60C
2
10
CH33-60D
2
3
CH33-62D
2
10
CR33-50/60
2
12
CR33-60
2
12
CX34-49C
0
0
CX34-60
1
4
CX34-62C
0
9
CX34-62D
CBX25UH-060
2
8
CBX25UHV-060
0
15
CBX26UH-060
3
9
CBX27UH-060
2
8
CBX32M-060
0
8
CBX32MV-048
0
8
CBX32MV-060
2
2
CBX32MV-068
2
2
CBX40UHV-048
-060
2
2
CBX40UHV-060
2
2
CH23-68
2
2
CH33-50, -60C
1
5
CH33-62D
3
2
CR33-50/60
1
0
CR33-60
0
0
CX34-62C
1
0
CX34-62D
105
110
115
VAP/LIQ
VAP/LIQ
VAP/LIQ
142/395
145/421
146/481
147/426
147/454
148/483
147/426
148/452
149/480
150/412
151/441
153/471
140/398
141/426
142/455
144/395
146/422
147/450
142/406
143/434
144/463
Additional
Subcool
Charge
Cool
Heat
lbs
oz
(+5ºF)
(+1ºF)
16
6
1
6
10
9
3
4
12
8
0
9
19
7
1
7
29
5
0
4
29
5
0
4
11
6
1
4
25
8
1
15
8
8
1
4
8
11
3
10
11
7
1
15
15
6
2
5
20
10
3
11
16
6
0
0
12
6
1
4
16
6
0
0
20
8
1
0
16
6
0
0
20
8
1
0
10
8
4
5
16
6
0
0
20
8
1
0
24
6
2
8
17
6
1
5
18
6
0
13
13
7
3
6
19
6
1
1
19
6
1
1
10
6
1
9
28
7
3
14
10
6
3
12
14
7
3
12
15
6
2
0
31
6
3
0
13
7
0
8
17
5
1
4
20
6
0
0
17
5
1
4
11
8
2
12
20
6
0
0
17
5
1
4
27
7
0
13
11
4
0
0
19
6
2
4
19
6
2
4
23
6
1
3
10
7
2
14
19
7
3
2

Advertisement

Table of Contents
loading

Table of Contents