Evacuating Line Set, Indoor Coil And Outdoor Unit - Lennox 13ACD-018-230 Installation Instructions Manual

13acd series split system air conditioner with dry nitrogen holding charge
Table of Contents

Advertisement

Evacuating Line Set, Indoor Coil and Outdoor Unit

1
CONNECT GAUGE SET
NOTE — Remove cores from service valves (if not already done).
Connect low side of manifold gauge set
with 1/4 SAE in-line tee to vapor line
service valve
Connect high side of manifold gauge set
to liquid line service valve
Connect
micron
connector on the 1/4 SAE in-line tee.
Connect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port line
will be used later for both the HCFC-22
and nitrogen containers.
NITROGEN
HCFC-22
2
EVACUATE THE SYSTEM
A
Open the liquid and vapor line service valves (counterclockwise) to release the factory nitrogen charge (contained in outdoor unit) into the
system.
B
Open both manifold valves and start the vacuum pump.
C
Evacuate the line set, indoor unit and outdoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE — The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
D
When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
Close manifold gauge valves
Close valve on vacuum pump
Turn off vacuum pump
Disconnect manifold gauge center port hose from vacuum pump
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
E
Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
F
Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
G
When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HCFC-22 refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor
unit.
H
Perform the following:
Close manifold gauge valves.
Shut off HCFC-22 cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.
506694-01
OUTDOOR
UNIT
gauge
available
VACUUM PUMP
Figure 10. Evacuating System
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
A
C
B
D
Issue 1720
MANIFOLD
GAUGE SET
500
MICRON
GAUGE
TO VAPOR
SERVICE VALVE
TO LIQUID LINE
SERVICE VALVE
RECOMMEND MINIMUM 3/8" HOSE
LOW
HIGH
1/6 TURN
12
1
11
2
10
9
3
4
8
5
7
6
Page 13 of 16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents