Download Print this page

Samson 3730-3 Safety Manual page 7

Electropneumatic positioner with hart communication 3730 series
Hide thumbs Also See for 3730-3:

Advertisement

Type 3730-3 Positioner: also observe the technical data in the test certificates for explosion-protected versions
Sensitivity
Transit time
To fill actuator
Air output
with air
capacity
To vent actuator
Permissible ambient tem-
perature
Use in safety-instrumented
systems (SIL)
Safety-relevant options
Solenoid valve · Approval according to IEC 61508/SIL · Emergency venting function
Input
Signal '0' (no response)
Signal '1' (response)
Service life
K
coefficient
V
Use in safety-instrumented
systems acc. to IEC 61508/
SIL
Inductive limit contact by Pepperl+Fuchs · Function: safety-related end position monitoring
For connection to switching amplifier according to EN 60947-5-6.
Can be used in combination with a software limit contact.
SJ2-SN proximity switch
SH 8384-3 EN
≤0.1 %
Venting or filling with air adjustable separately up to 240 s by software.
At Δp = 6 bar: 8.5 m
³/h · At Δp = 1.4 bar: 3.0 m
n
At Δp = 6 bar: 14.0 m
³/h · At Δp = 1.4 bar: 4.5 m
n
–20 to +80 °C (all versions)
–45 to +80 °C with metal cable gland
Observe the limits in the test certificate for explosion-protected versions.
Observing the requirements of IEC 61508, the systematic capability of the pilot valve
for emergency venting as a component in safety-instrumented systems is given.
Use is possible on observing the requirements of IEC 61511 and the required hard-
ware fault tolerance in safety-instrumented systems up to SIL 2 (single device/HFT = 0)
and SIL 3 (redundant configuration/HFT = 1).
24 V DC · Electrical isolation and reverse polarity protection · Static destruction limit
40 V
Current consumption I =
<12 V (emergency shutdown at 0 V)
> 19 V
>5 x 10
switching cycles
 6
0.15
Same as positioner pneumatics
Measuring plate not detected: ≥3 mA · Measuring plate detected: ≤1 mA
Technical data (excerpt from EB 8384-3)
U – 5.7 V
(corresponding to 4.8 mA at 24 V/114 mW)
3840 Ω
³/h · K
= 0.09
n
Vmax (20 °C)
³/h · K
= 0.15
n
Vmax (20 °C)
7

Advertisement

loading