Required conditions
Particle size and quantity
Class 4
≤ 5 µm and 1000/m³
Tip
We recommend installing a supply pressure regulator/filter upstream of the positioner.
For example, the SAMSON Type 4708 Supply Pressure Regulator with 5 µm filter car-
tridge can be used.
Î The supply air line has a minimum inside diameter of 4 mm.
Select the cross section and length of the line to ensure that the supply pressure at the po-
sitioner on filling the actuator with air does not fall below the minimum limit.
Î The positioner is mounted as prescribed.
Î The vent opening at the back of the positioner remains open when the positioner is in-
stalled on site.
Electrical installation
Î The positioner is connected to the electric power supply properly as described in the
mounting and operating instructions.
Î Only cables whose outside diameters are suitable for the cable glands are used.
Î The electrical cables in Ex i circuits comply with the data that planning was based on.
Î The cable glands and cover screws are fastened tightly to ensure that the degree of pro-
tection is met.
Î The installation requirements for the applicable explosion protection measures are ob-
served.
Î The special conditions specified in the explosion protection certificates are observed.
Operation
Î When the optional inductive limit contact is used, Code 38 is set to YES.
Î The inductive limit contact is adjusted mechanically to meet the specifications.
12
Oil content
Pressure dew point
Class 3
Class 3
≤ 1 mg/m³
–20 °C or at least 10 K below the lowest ambi-
ent temperature to be expected
SH 8384-3 EN