• When thermistor is abnormal.
Check of outdoor thermistors
Disconnect the connector in the following table and
measure the resistance of the thermistor to check
whether the thermistor is normal or not. (Refer to 11-7.)
Normal
Reconnect the connector in the following table and
disconnect the lead wire leading to the compressor.
3 minutes after turning ON the power supply,
start EMERGENCY OPERATION.
Does the unit operate 10 minutes or more without
showing thermistor abnormality?
Yes
Normal
Thermistor
Defrost
Discharge temperature
Outdoor heat exchanger temperature
Ambient temperature
Fin temperature
OBH723D
Abnormal
No
Symbol
Connector, Pin No.
Between CNTH1 pin1 and pin2
RT61
RT62
Between CNTH1 pin3 and pin4
RT68
Between CNTH1 pin7 and pin8
RT65
Between CNTH2 pin1 and pin2
RT64
Between CN171 pin1 and pin2
98
(MXZ-4E83VA/5E102VA/2E53VAHZ)
Replace the thermistor.
(MXZ-3E54VA/3E68VA/4E72VA/4E83VAHZ)
Replace the thermistor except RT64.
If RT64 is abnormal, replace the outdoor power
P.C. board since RT64 is combined with this board.
Replace the outdoor control P.C. board or the
outdoor power P.C. board.
Outdoor control P.C. board
Outdoor power P.C. board
Board