Mitsubishi Electric MXZ-3E54VA-E1 Service Manual page 97

Outdoor unit
Hide thumbs Also See for MXZ-3E54VA-E1:
Table of Contents

Advertisement

• When heating, room does not get warm.
• When cooling, room does not get cool.
How to check inverter/compressor
Disconnect the terminal of the compressor or the connector (CNMC) between the compressor
and the outdoor power P.C. board. 3 minutes after the power supply is turned ON,
start EMERGENCY OPERATION.
Measure the voltage between each
lead wire leading to the compressor.
U (BLK) - V (WHT)
V (WHT) - W (RED)
W (RED) - U (BLK)
Output voltage: 50V-250V
Is proper output voltage detected?
Is output balanced?
Is the input voltage to the outdoor control
P.C. board 370 V or more?
Turn OFF the power supply of indoor and
outdoor unit, and measure the compressor
winding resistance between the compressor
terminals.
Is the resistance between each terminal normal?
(Refer to 11-5.)
Reconnect the lead wire of compressor, and turn ON
the power supply to indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.
Clarify the causes by counting time until the inverter stops.
0 to 10 seconds: compressor layer short
10 to 60 seconds: compressor lock
60 seconds to 5 minutes: refrigerant circuit defective
5 minutes or more: normal
OBH723D
1 • After the outdoor fan starts running, wait for 1 minute
• The output voltage values have the tolerance of ± 20%.
2 • The output differs depending on the capacity or the
No
1,
2
Yes
No
Yes
Yes
Yes
or more before measuring the voltage.
number of indoor units to be operated.
No
Replace the outdoor power P.C. board.
No
Replace the compressor.
97