Quiet Mode; Comfort Sleep Mode; Short Timer - Toshiba RAS-18N3KCV Service Manual

Hide thumbs Also See for RAS-18N3KCV:
Table of Contents

Advertisement

Item

13. QUIET mode

When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L
again (cancel Quiet mode).
14. COMFORT
Cooling mode
SLEEP
• The preset temperature will increase as below.
• Press the [COMFORT SLEEP] button to
choose the operating hours. Repeat
pressing to select the hours.
(1hr, 3hr, 5hr or 9hr)
• If the [COMFORT SLEEP] button is pressed
again means cancel comfort sleep mode.
TA
+6.5
+6.0
+5.5
+5.0
+4.5
+4.0
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
TSC
-0.5
-1.0
-2.0
1H

15. Short Timer

In the normal condition, after switching one circuit
breaker, 3-minute delay time for compressor are
set for the maintenance of the unit.
Operation flow and applicable data, etc.
until the [QUIET] button is pressed once
2H
3H
4H
1
S WING
FAN
ONE-TOUCH
F IX
QUIE T
POWER-SEL
Hi POWER
C OMFOR T
S LE E P
3
Quiet mode is the system which, control the
revolving speed of indoor fan to work
constantly at lower than speed L. In addition,
noise level of indoor unit is less than usual.
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
cooling load condition. Because of the fan
speed L- may cause not enough the cooling
capacity or heating capacity.
The principles of comfort sleep mode are:
• Quietness for more comfortable. When
room temperature reach setting temperature
• Save energy by changing room temperature
automatically.
• The air condition can shut down by itself
automatically.
Remarks:
Comfort sleep mode will not operate in dry
mode and fan only mode.
Zone Frequency
FAN
12
Dry Max
11
*12
10
*11
*10
9
8
*9
7
*8
6
5
4
3
2
Min
1
* 12 (DRY max - COOL min) /6 x 5 + COOL min
Hz
* 11 (DRY max - COOL min) /6 x 4 + COOL min
* 10 (DRY max - COOL min) /6 x 3 + COOL min
* 9 (DRY max - COOL min) /6 x 2 + COOL min
* 8 (DRY max - COOL min) /6 x 1 + COOL min
OFF
Note : DRY max for calculation only.
Time
Purpose
To start the unit immediately for the purpose of
testing, trial...etc, short timer can be used.
maintenance of the unit.
Short Timer Setting
j
k
l
m
n
3
35
FILE NO. SVM-12053
Description
.
Press [
] button to turn the unit OFF
Set the operation mode or plasma air
purifier on the remote control without
sending the signal to the unit.
Use the tip of the pencil to push the
[CHK] button and hold, "00" will show
on display, them press [SET] button
to make "00" disappear.
Press [
] button to turn the unit ON.
When short timer is activated, all
setting on the remote operates
immediately, besides, all indicatiors on
front panel turns ON continuously for
3 seconds.
.