Rheem RGRJ series Installation Instructions Manual page 15

Upflow & downflow/horizontal high efficiency condensing gas furnaces
Table of Contents

Advertisement

BTUH
Free Area
Input
Each Opening
45,000
100 square inches
60,000
100 square inches
75,000
100 square inches
90,000
100 square inches
105,000
105 square inches
120,000
120 square inches
B. USING OUTDOOR AIR FOR
COMBUSTION
IMPORTANT: Do not take air
from an attic space that is
equipped with power ventilation.
The confined space must
communicate with the outdoors in
accordance with Methods 1 or 2.
The minimum dimension of air
openings shall not be less than 3
inches. Where ducts are used,
they shall be of the same cross-
sectional area as the free area of
the openings to which they
connect.
Method 1
Two permanent openings, one
located within 12 inches of the top
and one located within 12 inches
of the bottom of the enclosure,
shall be provided. The openings
shall communicate directly, or by
ducts, with the outdoors or spaces
(crawl or attic) that freely
communicate with the outdoors.
a. Where directly communicating
with the outdoors or where
communicating to the outdoors
through vertical ducts as shown in
Figure 11, each opening shall
FIGURE 11
AIR FROM ATTIC/CRAWL SPACE
OUTLET AIR
IN ATTIC
MUST BE
ABOVE
INSULATION
1 SQ. INCH PER
4000 BTUH
OUTLET AIR
FURNACE
GAS
WATER
HEATER
1 SQ. INCH PER
4000 BTUH INLET AIR
FIGURE 10
AIR FROM HEATED SPACE
have a minimum free area of 1
square inch for each 4,000 BTUH
of total appliance input rating in the
enclosure.
BTUH
Input
Each Opening
45,000
11.25 square inches
60,000
15.00 square inches
75,000
18.75 square inches
90,000
22.50 square inches
105,000
26.25 square inches
120,000
30.00 square inches
b. Where communicating with
outdoors through horizontal ducts,
each opening shall have a
minimum free area of 1 square
GABLE
VENT
VENTILATED
ATTIC GABLE OR
SOFFIT VENTS
12" MAX.
FURNACE
GAS
WATER
HEATER
Free Area
Round Pipe
Size
4"
5"
5"
6"
6"
6"
FIGURE 12
OUTSIDE AIR USING A HORIZONTAL DUCT
GAS
WATER
HEATER
NOTE:
EACH OPENING SHALL
HAVE A FREE AREA OF
NOT LESS THAN ONE
SQUARE INCH PER
1,000 BTU PER H0UR OF
THE TOTAL INPUT
RATING OF ALL
EQUIPMENT IN THE
ENCLOSURE, BUT NOT
LESS THAN 100
SQUARE INCHES.
inch for each 2,000 BTUH of total
input rating of all equipment in the
enclosure.
Here are some typical sizes.
BTUH
Free Area
Input
Each Opening
45,000
22.50 square inches
60,000
30.00 square inches
75,000
37.50 square inches
90,000
45.00 square inches
105,000
52.50 square inches
120,000
60.00 square inches
Method 2
One permanent opening, located
within 12 inches of the top of the
enclosure, shall be permitted
OUTLET AIR 1 SQ. INCH
PER 2000 BTUH
FURNACE
INLET AIR 1 SQ. INCH
12"
PER 2000 BTUH
MAX.
Round Pipe
Size
6"
6"
7"
8"
8"
9"
15