5.9

Standard Bistable Function Blocks

Standard bistable function blocks (Set-dominant)

SR(_E)
High
Basic
Process
Redundant Universal
performance
Structured ladder/FBD
SR_E
EN
ENO
s1
d
s2
The following function(s) can go in the dotted squares.
SR, SR_E
■Argument
Input/output
Name
argument
Input argument
EN
s1(_S1)
s2(RESET)
Output argument
ENO
d(Q1)
Processing details
■Operation processing
Sets (d) when (s1) is turned ON and resets (d) when (s2) is turned ON while (s1) is OFF. (d) is not reset even when (s2) is
turned ON while (s1) is ON.
■Operation result
• Function without EN/ENO
An operation is executed and the operation value is output from (d).
[Timing chart]
ON
ON
s1
OFF
OFF
ON
s2
OFF
ON
ON
d
OFF
OFF
Sets
d
when
= ON.
Resets
s1
LCPU
ST
SR_E
(EN, s1, s2, ENO, d);
Description
Executing condition (TRUE: Execution, FALSE:
Stop)
Input
Execution result (TRUE: Normal, FALSE: Error or
stop)
Output
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF
d
when
= OFF and
s2
= ON.
s1
Data type
Bit
Bit
Bit
Bit
ON
ON
OFF
OFF
ON
ON
ON
ON
OFF
OFF