Fujitsu AUYG07LVLA Design & Technical Manual page 30

Hide thumbs Also See for AUYG07LVLA:
Table of Contents

Advertisement

Fig 3
Outdoor
Indoor unit
temperature
connecting
16.0°C DB
DB
WB
capacity (%)
TC
°C
°C
-15.0
-16.0
10.5
-10.0
-11.0
12.8
-5.0
-7.0
14.4
0.0
-2.0
15.7
100
5.0
3.0
17.0
7.0
6.0
18.5
10.0
8.0
18.6
15.0
10.0
18.8
20.0
15.0
19.0
B-3: Capacity change rate by temperature conditions
(c) / (a) = 17.5 / 16.0 = 1.094 (Example 3)
(c') / (a) = 16.2 / 16.0 = 1.013 (Example 4)
Indoor temperature
18.0°C DB
IP
TC
IP
5.55
10.0
5.52
5.60
12.2
5.61
5.70
13.8
5.78
5.76
15.1
5.78
5.76
16.2
5.61
5.70
17.4
5.35
5.56
17.5
5.25
5.19
17.6
4.80
4.63
17.8
4.45
(c')
(c)
- (02 - 11) -
20.0°C DB
24.0°C DB
TC
IP
TC
IP
9.6
5.50
9.2
5.48
11.8
5.62
11.3
5.64
13.3
5.75
12.9
5.72
14.5
5.74
13.8
5.68
15.0
5.23
14.0
4.92
16.0
5.07
14.5
4.55
16.2
4.80
14.7
4.53
16.4
4.61
15.0
4.33
16.7
4.36
15.4
4.08
(a)
2. MODEL SELECTION