Conditions of Safe Use for Installation in Hazardous Locations
The following information applies to products bearing the UL marking for Hazardous
areas and the ATEX marking for Zone 2 explosive atmospheres:
Suitable for use in Class I Division 2 Groups A, B, C, D (applicable to 7'', 10'', 12'', and
15'' Display units).
Suitable for use in Class I Division 2 Groups A, B, C, D; Class 2 Division 2 Groups F, G;
Class 3 Division 1 and Division 2 (applicable only to only 6'' Display unit).
Suitable for Group II, Category 3, Gas Groups IIC, Dust Group IIIC (applicable only to
the IC755CxS12CDBCA and IC755CxS15CDACA Display units):
The equipment shall only be used in an area of at least pollution degree 2, as defined
1.
in IEC 60664-1.
Note Pollution degree 2 can be achieved when the installation is in a controlled
environment with suitably controlled condensation or airborne pollution
2.
The equipment shall be installed in an enclosure that provides a minimum ingress
protection of IP 54 in accordance with IEC 60079-0.
3.
Transient protection shall be provided that is set at a level not exceeding 140% of the
peak rated voltage value at the supply terminals to the equipment.
USB retaining clamp must be used in hazardous location installations as follows:
Connect the USB cable.
1.
2.
Insert the retaining clamp in the port above the USB connector.