Rules For Installing The N3700 In A Rack - IBM System Storage N3700 Hardware And Service Manual

N series
Table of Contents

Advertisement

Rules for installing the N3700 in a rack

You need to observe the following rules and restrictions when installing an N3700 in
a standard 19-inch (48.26 cm) equipment rack with mounting rails:
4
IBM System Storage N series: N3700 Hardware and Service Guide
Table 1. N3700 characteristics hardware specifications (continued)
Clearance dimensions
Front-cooling
Rear-cooling
Rear-maintenance
Environmental requirements
Note: Operating at the extremes of the following environmental requirements might
increase the risk of device failure.
Operating temperature maximum range
Operating temperature recommended range
Nonoperating temperature range
Relative humidity
Recommended operating temperature
relative humidity range
Maximum wet bulb temperature
Maximum altitude
Acoustic level
Electrical requirements
Input voltage, V
Input current actual, A
Maximum electrical power
Input power actual, with all drives writing, W
Input power actual, by JEL measurements,
W
Thermal dissipation, BTU/hr
Inrush current, A @ V
All versions
6 in. (15.3 cm)
All versions
12 in. (30.5 cm)
All versions
12 in. (30.5 cm)
50° F to 104° F
(10° C to 40° C)
68° F to 77° F
(20° C to 25° C)
-40° F to 149° F
(-40° C to 65° C)
10 to 90%
noncondensing
40 to 55%
28° C (82° F)
3050 m (10,000 ft.)
56.4 dBA @ 23° C
5.64 bels @ 23° C
100-120/200-240
4/2
100 to 120 VAC, 7
A/200 to 240 VAC,
3.5 A; 50/60Hz
440
389
1,215
25 @ 110/50 @ 220

Advertisement