Erase Enocean Devices; Erase Current Integrated Device; Erase All Devices In A Device Node - ABB i-bus KNX Product Manual

Knx/enocean gateway
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement


®
i-bus
KNX
is possible to check that the device has been learned in the numeric indicator of the LCD
display.
When learning EnOcean gateways for AC, the process will last few seconds and meanwhile the
"ongoing" text will be shown in the LCD.
In the specific case of rocker buttons, keep in mind that the A0 button needs to be pressed in
order to link the device properly and in a coherent way (see
In case of teach-in process, first press the Learn button of the EnOcean device that has to learn
the KNX/EnOcean Gateway chipID. Once the device is ready to receive other EnOcean devices
information, press the Teach button of our gateway. A "T" appears on the right side of the LCD
display indicating Teach-in process is running. For more information on how to activate the
Learn mode of the EnOcean device, please consult its user manual.
Three different erase modes are available: erase the current device, erase all devices in the
current device node and erase all devices from all nodes.

6.2.1 Erase current integrated device.

First, use the arrow buttons (UP/DOWN) to move up to de desired device that you want to
erase. When pressing the Erase button an "E" appears on the right side of the LCD display.
Then the gateway will be in "Erase" mode. To erase the desired EnOcean device, click on the
de Learn/Teach-in button from the device and it will be erased. It is possible to check that the
device has been erased in the numeric indicator of the LCD display. This mode is only available
for integrated devices, not for simulated ones.

6.2.2 Erase all devices in a Device Node

If pressed long (more than 2 seconds) an option to erase the whole node will be shown (press
Erase button again to confirm).
In case you want to erase all devices in a node, please push the Erase button for 2 seconds.
The device will ask for erasing the current node. By pressing again the Erase button, we will
erase all devices in that node. The node itself will not be erased. This can only be done through
the plugin.
On the other hand, if you want to erase all devices in all nodes, push buttons 2,3,4 and 5 at the
same time. Display will prompt a message asking for erasing all nodes. By pressing Erase
button, all devices from all nodes will be erased.
Remember that nodes themselves will not be erased. This can only be done through the plugin.
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
EG/A 32.2.1
Button A0 Button B0
Button A1 Button B1
Figure 6.2 Indication on the rocker button that has to be pushed during teach-in process
 +49 (0) 6221 701 724
Figure 6.2
www.abb.com/knx
Technische Helpline / Technical Support
 +49 (0) 6221 701 434 E-Mail: knx.helpline@de.abb.com
User's manual r1.5 eng
).
27 / 47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2cdg 120 047 r0011

Table of Contents