Danfoss KP 15 Installation Manual

Danfoss KP 15 Installation Manual

Pressure switch

Advertisement

Quick Links

Installation guide

Pressure switch
KP 15, KP 17W, KP 17B, KP 25
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D,
R448A, R449A, R450A, R452A, R507A, R513A
For complete list of approved refrigerants, go to http://products.danfoss.com/all-products/
KP 15
man. (LP) / man. (HP) reset
CAUTION:
Do not install these controls on ammonia systems.
Ambient temperatures / Mounting requirements
t
min.:
-40 °F (-40 °C)
1
- 1 3 °F (- 25 °C) (PED approved products)
t
max.: 149 °F ( 65 °C)
1
CAUTION:
Do not mount the control in a position where dirt,
sediment, or oil will affect the operation of the control.
Enclosure
A: 10 – 32 UNC
Threads (4 holes)
CAUTION:
The mounting panel must be plane to avoid damage of control.
© Danfoss | DCS (jmn) | 2016.10
KP 15, KP 17B
auto. (LP) / man. (HP) reset
Test pressure (P
B:
Enclosure ~NEMA1
KP 15, KP 17W, KP 25
auto. (LP) / auto (HP) reset
)
test
p
test
510 psig (35 bar p
p
test
285 psig (20 bar p
max 1/8 in
(3 mm)
DKRCC.PI.CA0.B3.22 | 520H11520 | 1
max.
)
e
max.
)
e

Advertisement

loading

Summary of Contents for Danfoss KP 15

  • Page 1: Installation Guide

    Installation guide Pressure switch KP 15, KP 17W, KP 17B, KP 25 Refrigerants: R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A, R452A, R507A, R513A For complete list of approved refrigerants, go to http://products.danfoss.com/all-products/ KP 15 KP 15, KP 17B KP 15, KP 17W, KP 25 man.
  • Page 2 A-B close on LP drop A-B close on LP drop = Bellows movement on pressure drop HP signal option: See label for current wiring inside cover. A-D close on HP rise 2 | 520H11520 | DKRCC.PI.CA0.B3.22 © Danfoss | DCS (jmn) | 2016.10...
  • Page 3 Selected reset configuration may be protected against unauthorized actions applying a seal. Adjustment spindle(s) location KP 15 KP 15, KP 17B KP 15, KP 17W, KP 25 A. MAN./MAN. RESET B. AUTO/MAN. RESET C. AUTO./AUTO. RESET DKRCC.PI.CA0.B3.22 | 520H11520 | 3...
  • Page 4 Low pressure (LP) side setting High pressure (HP) side setting KP 15A with LP man. reset only KP 15, KP 17W, KP 17B and KP 25 KP 15, KP 17W, KP 17B and KP 25 KP 15A with convertible LP auto.

This manual is also suitable for:

Kp 25Kp 17wKp 17b