Kohler 14/20RESAL Installation Manual page 28

Residential/commercial generator sets
Hide thumbs Also See for 14/20RESAL:
Table of Contents

Advertisement

Generator Set
Note:
Connect A to A, B to B, PWR to PWR, and COM to COM.
See Section 1.10.2, Cable Specifications.
* RXT transfer switch with standard or combined interface/ load management board.
Do not use a load shed kit with a combined interface board.
1. Generator set terminal block. See Figure 1-17 for location. Check the decal on the generator set for terminal block connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. Communication cable Belden #8762 or equivalent 20 AWG shielded, twisted-pair cable (one pair).
4. Connect shields together as shown.
5. Leave one end of each cable shield disconnected at the last device.
6. 12 AWG or 14 AWG leads for PWR and COM.
Figure 1-25 Accessory Module Connections with 12--14 AWG Power Leads
28