SETTING ANALOG OUTPUT LEVELS
(0-20/4-20 mA)
0-20 mA
PRESS, 0-20 / 4-20 mA OPTION,
4-20 mA
FOR 2 SECONDS
OPTION
2 SECS
IS THE PANEL LOCKED?
N
INCREASE
USE INCREASE OR DECREASE KEYS
TO ADJUST SETTING
DECREASE
Fig. 26. Flow Chart 8: 0-20/4-20mA Analog Output Setup.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD
DISPLAY SHOWS:
'02' FOR 0-20 mA
'42' FOR 4-20 mA
INCREASE
USE INCREASE OR DECREASE KEYS
TO ADJUST SETTING
DECREASE
Y
DISPLAY SHOWS 'PL',
UNTIL KEY RELEASED
STORE
RESET
rE
33
PRESS STORE TO SAVE THE
NEW SETTING
OR
PRESS RESET OR WAIT 4 SECONDS
TO RESTORE OLD SETTING
NORMAL OPERATION