4.4.4 Optional Dynamic Brake Hardware Size B & C Controls
If optional DB resistor is to be used, connect it to the + and BR terminals, (see Figure 4-2). Dynamic Brake (DB) Hardware
must be installed on a flat, non-flammable, vertical surface for effective cooling and operation. The DB Resistors get
extremely hot during normal operation and must be mounted away from flammable surfaces and unsafe atmosphere.
Nominal
Input
Hp
kW
Current
amps
0.5
.37
10.1
1
.75
18.9
1.5
1.1
25.5
0.5
0.37
6.7
1
0.75
10.5
2
1.5
16.2
2
1.5
16.2
3
2.2
23.8
0.5
0.37
3
1
0.75
5.7
2
1.5
8.4
2
1.5
8.4
3
2.2
13.1
5
4
17.3
1
0.75
3.1
2
1.5
4.8
2
1.5
4.8
3
2.2
7.2
5
4
10.8
7.5
5.5
13.3
10
7.5
18.5
For UL compliance Motor Cable to be Copper 75°C and Fuse current rating defined by ratings marked ( )*.
Wire size is based on 40°C ambient and fuses are based on 45°C ambient, max continuous output and no harmonic current.

4.4.5 Motor Connections

All cables must be shielded and the shields must be grounded at the enclosure cable entrance.
1. Remove covers. Cover removal is described in Chapter 3 of this manual.
2. Connect the Motor leads to terminals U, V and W (see Figure 4-2 for location).
3. Connect the motor ground wire to the ground terminal (See Figure 4-2).

4.4.6 Long Motor Leads

The wire leads that connect the motor to the control are critical in terms of sizing, shielding and the cable characteristics.
Short cable runs are usually trouble free but fault-monitoring circuitry can produce numerous faults when long cables are
used. Refer to Table 4-1 for maximum cable lengths. Baldor recommends adding an optional load reactor to the output of
the control. The load reactor and/or common mode choke should be placed in close physical proximity to the control.
MN762
Table 4-1 Fuse & Wire size / Terminal Torque Specifications
Fuse or
Supply Cable
MCB
Size
amps
AWG
mm2
110-115V +/-10% 1-Phase Input, 230V 3-Phase Output
16 (15)*
14
2.5
25
10
4
32 (35)*
8
6
200-240V +/-10% 1-Phase Input, 230V 3-Phase Output
10
14
1.5
16 (15)*
14
2.5
20
10
4
20
10
4
25
10
6
200-240V +/-10% 3-Phase Input
6
14
1.5
10
14
1.5
10
14
2.5
10
14
2.5
16 (15)*
12
4
20
10
4
380-480V +/-10% 3-Phase Input
6
14
1.5
6
14
1.5
6
14
1.5
10
14
1.5
16 (15)*
14
2.5
16 (15)*
12
4
25
10
4
Nominal
Motor Cable
Torque
Output
Size
Lb-in
Current
(Nm)
Amps
AWG
9.0 (1.0)
2.3
14
9.0 (1.0)
4.3
14
9.0 (1.0)
5.8
14
9.0 (1.0)
2.3
14
9.0 (1.0)
4.3
14
9.0 (1.0)
7
14
9.0 (1.0)
7
14
9.0 (1.0)
10.5
14
9.0 (1.0)
2.3
14
9.0 (1.0)
4.3
14
9.0 (1.0)
7
14
9.0 (1.0)
7
14
9.0 (1.0)
10.5
14
9.0 (1.0)
18
10
9.0 (1.0)
2.2
14
9.0 (1.0)
4.1
14
9.0 (1.0)
4.1
14
9.0 (1.0)
5.8
14
9.0 (1.0)
9.5
14
9.0 (1.0)
14
12
9.0 (1.0)
18
10
Max Motor
Torque
Cable Length
Lb-in
(Nm)
mm2
Feet
Meters
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
328
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
328
1.5
9.0 (1.0)
328
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
328
1.5
9.0 (1.0)
328
2.5
9.0 (1.0)
328
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
82
1.5
9.0 (1.0)
164
1.5
9.0 (1.0)
164
1.5
9.0 (1.0)
164
2.5
9.0 (1.0)
328
2.5
9.0 (1.0)
328
Min
Brake
Resistor
Value
Ohms
25
---
25
---
100
47
25
---
25
---
25
---
100
47
100
47
25
--
25
---
25
---
100
47
100
47
100
47
25
---
25
---
50
100
50
100
50
100
100
47
100
47
Power Wiring 4-3