2.3.3 Connecting the LV cables

Remove the vertical covers f the cable duct on front left in
the withdrawable unit compartment from the
side/partition wall. For this purpose remove the fixing bolts
(Fig.12). Run the LV cables on the left-hand side of each
panel, enter the cable into the LV cubicle and connect it
there. Fix the LV cables to the support plates (1,2Fig.13)
using cable connectors. Two rows of rectangular cutouts
are provided to the holding plates.
Fig.12 Sheetsteel covers for LV cables
Fig.13 Upper support Plate (1) and
lower support plate (2) for LV
cables (on the left-hand side of
the withdrawable unit
compartment)
1 Fixing bolt