Data point list for
normal operation
Current measured values
Limitation manipulated variable
Presettings
Unoccupied heating/cooling
mode
Night purging
Setpoints frost
protection / standby controller
Parameters frost
protection / standby
controller
Displacement ventilation
Control parameters room
temperature controller
Control parameters supply air
temperature controller
Switching points compressor
Summer compensation
Winter compensation
Alarm priorities
Time elements
HR anti-icing protection
CM2N3204E / 05.2001
16/20
Data point values and measured values can be called up under certain data point
numbers.
The controller is supplied with factory set values (bold print). These factory settings are
selected so that the controller suits a majority of plants.
Each of them can be changed, if required. The factory set data are stored in non-volatile
memory.
No.
Description
1
B9 Frost temperature
2
Z Input variable
3
F91 Common fault relay
1)
4
E7 Control input 1
1)
5
E8 Control input 2
6
Y30 Minimum limitation
7
Fan speed
8
Setpoint pair (Comfort/Economy)
9
Room temperature limit heating
10
Room temperature limit cooling
11
Minimum operating time
12
Room temperature limit
13
Outside temperature limit
14
Delta
15
Minimum operating time
16
Frost alarm value
17
Standby controller
18
P-band frost protection controller
19
P-band standby controller
20
TN standby controller
21
Disabling of fan speed 2 acc.
to outside temperature B4
22
Delta for heating
23
Delta for cooling
24
KE room (cascade authority)
25
TN
26
P-band heating
2)
27
TN heating
28
P-band heat recovery
2)
29
TN heat recovery
30
P-band cooling
2)
31
TN cooling
32
Switching interval SA
33
Switching differential SD
34
Starting point
35
End point
36
Delta
37
Starting point
38
End point
39
Delta
40
E1 Fire/smoke
41
E2 Air flow supervision
42
E3 Overload pump/electric
43
E4 Overload chiller
44
E5 Overload fan
45
E6 AUX, freely available
46
B9 Frost alarm
3)
47
Fan overrun time
48
Min. heating circulator running time
49
Heating circulator kick interval
50
Alarm delay air flow start
51
Alarm delay air flow operation
12)
52
Alarm delay AUX
53
E7, E8 control input on time 4)
54
Start-up time (damper fully closed)
55
Preheating time
13)
56
Power up start delay
57
Setpoint
58
P-band
2)
59
TN
Range
− 50.0...+150.0 °C
− 50.0...+150.0 °C/
0...2000 ppm
OFF/On
OFF/On
OFF/On
0...100 %
1/2
Co/Ec
0...30 °C
20...50 °C
00.00...12.00 hh.mm
10...50 °C
5...30 °C
1...20 K
00.00...12.00 hh.mm
2...30 °C
2...50 °C
1...30 K
1...200 K
00.00...10.00 mm.ss
− 50...+150 °C
14)
1...10 K
1...10 K
0...20.0
00.00...40.00 mm.ss
1...200 K
00.00...10.00 mm.ss
1...200 K
00.00...10.00 mm.ss
1...200 K
00.00...10.00 mm.ss
1...100 % of Y20
1...100 % of Y20
10...50 °C
10...50 °C
− 10...+10 K
− 30...+20 °C
− 30...+20 °C
− 10...+10 K
A / b
A / b
A / b
A / b
A / b
A / b
A / b
00.00...30.00 mm.ss
11)
00.00...30.00 mm.ss
10)
00.00...24.00 hh.mm/
Auto/Cont
12)
00.00...10.00 mm.ss
12)
00.00...10.00 mm.ss
00.00...05.00 mm.ss
00.00...12.00 hh.mm
5)
00.00...60.00 mm.ss
00.00...10.00 mm.ss
00.00...30.00 mm.ss
− 10...+30 °C
1...100 K
00.00...04.00 mm.ss
Factory setting
(Read value)
(Read value)
(Read value)
(Read value)
(Read value)
0 %
1
Co
15 °C
30 °C
00.30 hh.mm
22 °C
12 °C
5 K
00.30 hh.mm
5 °C
25 °C
5 K
7 K
03.00 mm.ss
− − − − 15 °C
4 K
3 K
2.0
08.00 mm.ss
20 K
02.30 mm.ss
15 K
02.00 mm.ss
15 K
02.00 mm.ss
20 %
10 %
25 °C
30 °C
2 K
5 °C
−20 °C
1 K
A
A
A
A
A
A
A
05.00 mm.ss
05.00 mm.ss
Auto
00.20 mm.ss
00.10 mm.ss
00.00 mm.ss
00.00 hh.mm
00.00 mm.ss
00.00 mm.ss
00.00 mm.ss
1 °C
10 K
01.00 mm.ss