Chapter 5 – Technical Specifications and Dimensions
Type: FPF-
Specification:
Voltage in V
Current in A at 40°C
Leakage current in
mA/phase/50Hz
worst case
1) 3)
Leakage current in
mA/phase/50Hz Un
2) 3)
Test voltage in V DC for 1s
ph./ground
Dimensions
Single wire / litze
Output cable
Weight in kg (approx.)
Heat dissipation
in W (approx.)
). "Worst case" states the leakage current for three-phase filters in the worst of cases.
1
That means one phase is live and two phases of the feed-line lead-in are interrupted.
These maximum values are based on an operating voltage of 460 V (ph./ph.).
2
) The normal leakage current for three-phase filters is stated. This means the filter is
operating on 460 V (ph./.ph.). The stated values are adhered to up to a neutral voltage of
5V to ground caused by line unbalance.
3
) (): Values when switch position is 0 (low leakage current)
Current
Overload
Frequency
Material
Humidity class
Chapter – Technical specifications and dimensions of NE-S1 filter
of NE-S1 Filter
FPF-9120-10-SW
FPF-9120-14-SW
240 +5%
240 +5%
2 x 8A
2 x 14A
36 (6.1)
55 (4.1)
< 20 (3.1)
< 31 (2.1)
1770
1770
6 mm²
6 mm²
2x2.5 mm²
2x2.5 mm²
0.5
1.0
2
5
at 40°C ambient temperature
1.5 x I N for 3min
50 / 60 Hz
Metal housing
IEC-Clamate-Category acc. to IEC60068-1:
25/100/21
FPF-9120-24-SW
FPF-9340-05-SW
240 +5%
2 x 24A
55 (6.1)
<31 (3.1)
1770
6 mm²
3x4 mm²
0.9
10
5-1
FPF-9340-10-SW
460 +5%
460 +5%
3 x 5A
3 x 11A
40 (24)
46 (3.4)
<2.4 (1.3)
<3.8 (0.2)
1770
1770
6 mm²
6 mm²
3x2.5 mm²
3x2.5 mm²
0.7
1.2
4
7