Phase Angle + Voltage + Current - HP 850F Operating Manual

Digital power clamp meter
Table of Contents

Advertisement

kWh value and the measuring time of the corresponding phase.
● The measuring reading gets increasing along with the time increases.
Press HOLD to read a particular time kWh value. Then the reading and time
are locked, but still continuous accumulate measuring time.
● After read the data, press HOLD again to continous measurement. kWh
value continous accumulate and the measuring time jumps to the present
measuring time.
● When the measuring time is over 24 hours or the Meter is switched to
other measuring ranges, active energy measuring will stop.
● The maximum reading of active energy is 9999kWh. 9999 will be
displayed when the reading is over than that.
5. MAX/▲ and MIN/▼ are not valid when measuring active energy.
6. Press CLEAR to reset the time.
Note
● When there is no input signal, it cannot carry out active energy
measurement.
● When there is input signal, the maximum waiting time is around 10s
before timing.
● When testing has been completed, disconnect the connection between
the testing leads and the circuit under test and remove testing leads from
the input terminals.
G. Phase Angle(φ)+Voltage(V)+Current(A)
φ
(1) Turn on
Rotary Switch to "
" function.
(2)Press the lever to open the transformer jaw, and clamp them to the
corresponding phase of tested conductor. If user needs to measure any
phase of the 3 phase, then clamp them to that phase's conductor.
(3) The connecting method of 3 phases 4 wires, 3 phases 3 wires or single
phase 2 wires, see figure 4, 5 and 6
(4) Press SELECT to choose the phase φA. See figure 24
figure 24
24