Constant Airflow Motors (Ecm) - Bosch LV009 Installation And Maintenance Manual

Lv series
Hide thumbs Also See for LV009:
Table of Contents

Advertisement

30 | Fan Motor Options
Table 8: Constant Torque Blower Motor Data
Rated
Model
Tap #
Airflow
1
2
LV-048
3
1600
4
5
1
2
LV-060
3
2000
4
5
1
2
LV-070
3
2100
4
5
updated 7/30/14

Constant Airflow Motors (ECM)

For installations where constant air delivery is critical or
where external static pressure drop can vary greatly
(such as with high MERV value filters) the LV series is
offered with a constant air flow ECM motor option. This
option provides ECM motor efficiency combined with a
constant air delivery across a wide range of external
static pressures. These motors dynamically adjust their
power output to precisely match the desired air flow on
a pre-programmed fan curve. Additionally these motors
feature:
1.
A low CFM ventilation feature that circulates air at
70% of full load when fan only is called.
2.
A passive dehumidification mode that reduces air
flow during a cooling call when dehumidification is
also required – this reduces the sensible heat ratio
of the cooling coil and extends cooling run time to
more effectively dehumidify. (refer to the ECM
Interface Board section of this manual)
3.
3 speed settings per model. Units are factory set to
"NORM" but can be field adjusted to "+" to increase
CFM by 15% or to "-"to reduce CFM by 15%. (refer
to the ECM Interface Board section of this manual)
4.
A "TEST" mode that operates the motor at a 70%
torque setting. This setting can be used to diagnose
programming problems in the motor itself. (refer to
the ECM Interface Board section of this manual)
8 733 944 336 (2016/09)
0.10
0.20
0.30
0.40
1390
1370
1350
1320
1600
1580
1550
1530
1730
1700
1670
1650
1830
1810
1780
1760
1930
1910
1880
1860
1900
1880
1860
1820
2000
1970
1950
1920
2110
2090
2060
2030
2220
2200
2170
2140
2340
2320
2290
2260
2050
2010
1970
1930
2150
2120
2080
2030
2270
2230
2200
2160
2390
2350
2320
2280
2520
2480
2450
2420
Subject to change without prior notice
0.50
0.60
0.70
0.80
-
-
-
-
1510
-
-
-
1630
1600
1580
1540
1740
1710
1670
1600
1830
1780
1720
1640
-
-
-
-
1890
1860
-
-
2010
1970
1940
1910
2110
2080
2050
2060
2230
2210
2180
2150
-
-
-
-
1990
1960
-
-
2120
2080
2040
2010
2250
2200
2160
2130
2380
2330
2290
2260
5.
A CFM indicator light that provides a blink for each
100 CFM of air delivered (note that this blink code
is approximate and should not replace test and
balancing).
Refer to the constant air flow motor performance
tables for heat pump blower performance with the
constant air flow motor option.
LV Heat Pump Series
0.90
1.00
1.10
1.20
-
-
-
-
-
-
-
-
-
-
-
-
1520
-
-
-
1540
1420
-
-
-
-
-
-
-
-
-
-
1880
-
-
-
2050
2000
1920
-
2110
2070
2000
1930
-
-
-
-
-
-
-
-
1980
-
-
-
2100
2070
2030
-
2220
2170
2100
2020
LV Heat Pump Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents