WATER QUALITY TABLE

Table 5: Water Quality
POTENTIAL PROBLEM
SCALING
CORROSION
IRON FOULING
EROSION
* No "rotten egg" smell present at < 0.5 ppm H2S.
** Equivalent to 30 mesh strainer

Condensate Connections

A drain line must be connected to the heat pump
and pitched away from the unit a minimum of 1/8"
per foot to allow the condensate to flow away from
the unit.
This connection must be in conformance with local
plumbing codes. A trap must be installed in the
condensate line to ensure free condensate flow.
(Heat Pumps are not internally trapped).
A vertical air vent is sometimes required to avoid air
pockets.
The depth of the trap depends on the amount of positive
or negative pressure on the drain pan. A second trap
must not be included.
The horizontal unit should be pitched approximately
1/4" towards the drain in both Duct System
All LV Series models are provided with a return air duct
flange and supply air duct connections.
LV Heat Pump Series
Water Characteristic
pH (Acidity/Alkalinity)
Hardness (CaCO3, MgCO3)
Ryznar Stability Index
Langelier Saturation Index
Hydrogen Sulfide (H2S)
Sulfates
Chlorine
Chlorides
Carbon Dioxide
Ammonia
Ammonia Chloride
Ammonia Nitrate
Ammonia Hydroxide
Ammonia Sulfate
Dissolved Solids
Iron (Fe2+ Iron Bacteria
Potential)
Iron Oxide
Suspended Solids
Maximum Water Velocity
Acceptable Value
Copper
7-9
< 350 ppm
6.0 - 7.5
-0.5 - +0.5
< 0.5 ppm *
< 125 ppm
< 0.5 ppm
< 20 ppm
< 50 ppm
< 2 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 1,000 ppm
< 0.2 ppm
< 1 ppm
< 10 ppm, < 600 μm size **
6 ft/sec
Refer to unit Dimensional Drawings for physical
dimensions of the collar and flange. Page# 55. A flexible
connector is recommended for supply and return air
duct connections on metal duct systems. All metal
ducting should be insulated with a minimum of 1" (one
inch) duct insulation to avoid heat loss or gain and
prevent condensate from forming during the cooling
operation. Application of the unit to non-insulated duct
work is not recommended as the unit's performance will
be adversely affected.
Water Quality Table | 23
Cupro-Nickel
7-9
< 350 ppm
6.0 - 7.5
-0.5 - +0.5
10-50 ppm
< 125 ppm
< 0.5 ppm
< 150 ppm
< 50 ppm
< 2 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 0.5 ppm
< 1,500 ppm
< 0.2 ppm
< 1 ppm
< 10 ppm, < 600 μm size **
6 ft/sec
8 733 905 683 (2016/09)