Control Of Device Functions; Display And Set Date And Time - Siemens siprotec 7SJ63 Instruction Manual

Multi-functional protective relay with local control
Hide thumbs Also See for siprotec 7SJ63:
Table of Contents

Advertisement

Operators Tools
7.2

Control of Device Functions

7.2.1

Display and Set Date and Time

Time Status
Representation of
the Time
7-28
The user can change individual functions and messages in a 7SJ63 while the device
is in-service. Some examples are given above, including erasing saved information
(Sub-section 7.1.1.5) and setting/resetting counters and limits (Sub-sections 7.1.2.2
and 7.1.3.4). In this section, three other control capabilities are discussed. They are
correcting the date and time, changing the settings group, and affecting information at
the SCADA interface during test operations.
The 7SJ63 device can be connected to an external synchronization signal, binary in-
put or use the internal RTC for time and date stamping.
Besides the display of date and time, the status of these readings is also provided. The
text of the status display can have the appearances given in Table 7-2, under regular
conditions of time control.
Table 7-2
Time Status
Status Text
No.
   
1
   67
2
  (5 
3
  (5 67
4
 16 (5 
5
 16  
6
The text symbols, or "status bits", for the time status have the following meanings:
16
Not synchronized
(5
Time Error
67
Daylight Savings
Time
Various representations of the date and time stamp may be given in the '$7(7,0(
sub-menu and in all messages stamped with the date and time. The year number and
the values of the status bits "time invalid" and "time malfunction" determine the repre-
synchronized
not synchronized
Time was neither set manually nor synchronized
after power-up.
At the moment, there is no cyclical synchronization
within the tolerance times (time can jump)
The latest synchronization signal received supplied a
daylight savings time bit
7SJ63 Manual
C53000-G1140-C120-1